4.4

Power Modules Chassis

4.4.1

Description

A Power Module is a power unit (frequency inverter) that provides the power supply for the
connected motor. A Power Module must be connected to a Control Unit via DRIVE-CLiQ.
The open-loop and closed-loop control functions are stored in the Control Unit.
Characteristics of Power Modules
● Version from 210 A to 490 A
● Internal air cooling
● Short-circuit/ground-fault-proof
● Electronic type plate
● Operating status and error status displayed using LEDs
● DRIVE-CLiQ interface for communication with the Control Unit and/or other components
● Integration in system diagnostics
4.4.2

Safety instructions for Power Modules chassis format

Danger to life if the fundamental safety instructions and residual risks are not observed
The non-observance of the fundamental safety instructions and residual risks stated in
Chapter 1 can result in accidents with severe injuries or death.
• Observe the fundamental safety instructions.
• Consider the residual risks for the risk evaluation.
Danger of fire through overheating for insufficient ventilation clearances
Insufficient ventilation clearances result in overheating with danger to persons as a result of
smoke and fire. Further, increased failures can occur and the service life of units/systems
shortened.
• Observe the cooling clearances above, below, and in front of the component, which are
AC Drive
Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4
in the drive line-up
WARNING
WARNING
specified in the dimension drawings.
Power Modules
4.4 Power Modules Chassis
159