APPENDIX F
SETPOINT > PROTECTION ELEMENTS >VOLTAGE ELEMENTS>AUXILIARY OV
AUXILIARY OV 1> AUXILIARY OV 2 > AUXILIARY OV 3
SETTING DESCRIPTION
Function permission
Pickup Level
Trip Time
Reset Time
Snapshot Event generation
SETPOINT > PROTECTION ELEMENTS >VOLTAGE ELEMENTS>AUXILIARY UV
AUXILIARY UV 1> AUXILIARY UV 2 > AUXILIARY UV 3
SETTING DESCRIPTION
Function permission
Pickup Level
Curve shape
Time Dial
Snapshot Event generation
SETPOINT > PROTECTION ELEMENTS >VOLTAGE ELEMENTS>VOLTS/HERTZ (ENHANCED MODELS ONLY)
VOLTS/HERTZ 1> VOLTS/HERTZ 2 > VOLTS/HERTZ 3
SETTING DESCRIPTION
Function permission
V/Hz Source for element calculations
V/Hz Minimum operating Voltage
V/Hz Pickup Level
V/Hz Curve
V/Hz TD Multiplier
V/Hz Reset Delay
Snapshot Event generation
SETPOINT > PROTECTION ELEMENTS >VOLTAGE ELEMENTS>GROUND OV
GROUND OV 1> GROUND OV 2 > GROUND OV 3
SETTING DESCRIPTION
Function permission
Pickup level
Trip Time
Reset Time
Snapshot event generation
GEK-113285A
NAME
DEFAULT VALUE
Function
DISABLED
Pickup Level
10
Trip Delay
10.00
Reset Delay
0.00
Snapshot Events
ENABLED
NAME
DEFAULT VALUE
Function
DISABLED
Pickup Level
10
Curve
DEFINITE TIME
Delay
10.00
Snapshot Events
ENABLED
NAME
DEFAULT VALUE
Function
DISABLED
V/Hz Source
PHASES
V/Hz Minimum Voltage 40.00
V/Hz Pickup Level
1.00
V/Hz Curve
DEFINITE TIME
V/Hz TD Multiplier
1.00
V/Hz Reset Delay
1.0
Snapshot Events
ENABLED
NAME
DEFAULT VALUE
Function
DISABLED
Pickup Level
10
Trip Delay
10.00
Reset Delay
0.00
Snapshot Events
ENABLED
G650 Generator Protection & Control System
F.1 FACTORY DEFAULT SETTINGS
STEP
RANGE
N/A
[DISABLED – ENABLED]
1 V
[3 : 500]
0.01 s
[0.00 : 900.00]]
0.01 s
[0.00 : 900.00]
N/A
[DISABLED – ENABLED]
STEP
RANGE
N/A
[DISABLED – ENABLED]
1 V
[3 : 500]
[DEFINITE TIME –
N/A
INVERSE TIME]
0.01 s
[0.00 : 900.00]
N/A
[DISABLED – ENABLED]
STEP
RANGE
N/A
[DISABLED – ENABLED]
N/A
[PHASES – AUX
VOLTAGE]
0.01 V
[30.00 : 500.00]
0.01 pu
[0.80 : 4.00]
[DEFINITE TIME-CURVE
A-CURVE B – CURVE C]
0.01
[0.05 : 600.00]
0.1 s
[0.0 : 900.0]
N/A
[DISABLED – ENABLED]
STEP
RANGE
N/A
[DISABLED – ENABLED]
1 V
[3 – 500]
0.01 s
[0.00 – 900.00]
0.01 s
[0.00 – 900.00]
N/A
[DISABLED – ENABLED]
USER
VALUE
USER
VALUE
USER
VALUE
F
USER
VALUE
F-13