GE Multilin G650 Manual page 495

Generator protection & control system
Hide thumbs Also See for Multilin G650:
Table of Contents

Advertisement

B.7 MEMORY MAP
ADDRESS BIT
Ajustes Sobreintensidad Instantánea de Tierra Sensible Grupo 2 - Sensitive Ground IOC 2 Settings (Enhanced models only)
0x236D
0x236E
0x236F
B
0x2371
0x2373
0x2375
0x2388
Ajustes Sobreintensidad Instantánea de Tierra Sensible Grupo 3 - Sensitive Ground IOC 3 Settings (Enhanced models only)
0x2389
0x238A
0x238B
0x238D
0x238F
0x2391
0x23A4
Ajustes Sobreintensidad Temporizada de Fases Nivel Alto Grupo 1 - Phase TOC High 1 Settings
0x23A5
0x23A6
0x23A7
0x23A9
0x23AA
0x23AC
B-68
NAME
Function
Input
Pickup Level
Trip Delay
Reset Delay
Snapshot Events
Confirmation address
Function
Input
Pickup Level
Trip Delay
Reset Delay
Snapshot Events
Confirmation address
Function
Input
Pickup Level
Curve
TD Multiplier
Reset
G650 Generator Protection & Control System
FORMAT STEP MODE LENGTH MISCELLANEOUS
F012
1
R/W
1
F012
1
R/W
1
F003
1
R/W
2
F003
1
R/W
2
F003
1
R/W
2
F012
1
R/W
1
W
1
F012
1
R/W
1
F012
1
R/W
1
F003
1
R/W
2
F003
1
R/W
2
F003
1
R/W
2
F012
1
R/W
1
W
1
F012
1
R/W
1
F012
1
R/W
1
F003
1
R/W
2
F012
1
R/W
1
F003
1
R/W
2
F012
1
R/W
1
APPENDIX B
0=DISABLED
1=ENABLED
0=PHASOR(DFT)
1=RMS
[0.005 , 16.000] A
[0.00 , 900.00] s
[0.00 , 900.00] s
0=DISABLED
1=ENABLED
0=DISABLED
1=ENABLED
0=PHASOR(DFT)
1=RMS
[0.005 , 16.000] A
[0.00 , 900.00] s
[0.00 , 900.00] s
0=DISABLED
1=ENABLED
0=DISABLED
1=ENABLED
0=PHASOR(DFT)
1=RMS
[0.05 , 160.00] A
0=IEEE Ext Inv
1=IEEE Very Inv
2=IEEE Mod Inv
3=IEC Curve A
4=IEC Curve B
5=IEC Curve C
6=IEC Long-Time Inv
7=IEC Short-Time Inv
8=IAC Ext Inv
9=IAC Very Inv
10=IAC Mod Inv
11=ANSI Ext Inv
12=ANSI Very Inv
13=ANSI Norm Inv
14=ANSI Mod Inv
15=I2t
16=Definite Time
17=Rectifier Curve
18=User Curve A
19=User Curve B
20=User Curve C
21=User Curve D
[0.00 , 900.00] s
0=INSTANTANEOUS
GEK-113285A