5.4 PROTECTION ELEMENTS
5.4.2.3
IAC CURVES
This family of curves follows the time response of the General Electric IAC electromechanical relays. The following
formulas define these curves:
Where:
t = Operation time in seconds
Dial = multiplier setting
I = Input current
Itap = Current pickup value
A, B, C, D, E = predefined constants
T
= reset time in seconds
RESET
t
= characteristic constant.
r
5
Table 5–33: CONSTANTS FOR IAC CURVES
IAC CURVE SHAPE
IAC Extremely Inverse
IAC Very Inverse
IAC Inverse
5-34
NAME
A
B
IAC Ext Inv
0.0040
0.6379
IAC Very Inv
0.0900
0.7955
IAC Mod Inv
0.2078
0.8630
G650 Generator Protection & Control System
C
D
E
0.6200
1.7872
0.2461
0.1000
-1.2885
7.9586
0.8000
-0.4180
0.1947
5 SETTINGS
TR
6.008
4.678
0.990
GEK-113285A