5 SETTINGS
The 1 pu value for V/Hz operation is the Nominal Voltage setting divided by the Nominal Frequency setting adjusted in the
General Settings menu.
The characteristics of the inverse curves are shown below:
DEFINITE TIME: T (sec) = TD Multiplier.
INVERSE CURVE A:
where:
T = operating time
TDM = Time Delay Multiplier (sec)
V = fundamental value of voltage (pu)
F=frequency of voltage signal (pu)
Pickup= volts-per-hertz pickup setpoint (pu)
INVERSE CURVE B:
where:
T = operating time
TDM = Time Delay Multiplier (sec)
V = fundamental value of voltage (pu)
F=frequency of voltage signal (pu)
Pickup= volts-per-hertz pickup setpoint (pu)
INVERSE CURVE C:
where:
T = operating time
TDM = Time Delay Multiplier (sec)
V = fundamental value of voltage (pu)
F=frequency of voltage signal (pu)
Pickup= volts-per-hertz pickup setpoint (pu)
GEK-113285A
TDM
=
T
2
V
Pickup
F
TDM
=
T
V
Pickup
F
TDM
=
T
0
5 .
V
Pickup
F
G650 Generator Protection & Control System
5.4 PROTECTION ELEMENTS
>
whenV
/
F
Pickup
1
>
whenV
/
F
Pickup
1
>
whenV
/
F
Pickup
1
5
5-69