Section 9
Testing IED operation
9.5
72
IL1
IL2
IL3
IN
UL1
UL2
UL3
UN
IEC09000652 V1 EN
Figure 10:
Connection example of the test equipment to the IED when test
equipment is connected to the transformer input module

Releasing the function to be tested

Release or unblock the function to be tested. This is done to ensure that only the
function or the chain of functions to be tested are in operation and that other functions
are prevented from operating. Release the tested function(s) by setting the
corresponding Blocked parameter under Function test modes to No in the local HMI.
When testing a function in this blocking feature, remember that not only the actual
function must be activated, but the whole sequence of interconnected functions (from
measuring inputs to binary output contacts), including logic must be activated. Before
starting a new test mode session, scroll through every function to ensure that only the
function to be tested (and the interconnected ones) have the parameters Blocked and
eventually EvDisable set to No and Yes respectively. Remember that a function is also
blocked if the BLOCK input signal on the corresponding function block is active,
which depends on the configuration. Ensure that the logical status of the BLOCK
input signal is equal to 0 for the function to be tested. Event function blocks can also
be individually blocked to ensure that no events are reported to a remote station during
the test. This is done by setting the parameter EvDisable to Yes.
Any function is blocked if the corresponding setting in the local HMI
under Main menu/Test/Function test modes menu remains On, that
is, the parameter Blocked is set to Yes and the parameter TestMode
under Main menu/Test/IED test mode remains active. All functions
that were blocked or released in a previous test mode session, that is,
IL1
IL2
IL3
IN (I4,I5)
UL1
UL2
UL3
UN
UN (U4,U5)
TRIP L1
TRIP L2
TRIP L3
IEC 61850
IEC09000652-1-en.vsd
1MRK 511 360-UEN A
Bay control REC670 2.1 IEC
Commissioning manual