Wiring; Terminal Connection Diagram; Main Circuit; Control Circuit - Mitsubishi Electric FR-A700 Series Instruction Manual

Hide thumbs Also See for FR-A700 Series:
Table of Contents

Advertisement

Wiring

2.4 Wiring
2.4.1

Terminal connection diagram

Sink logic
*1. DC reactor (FR-HEL)
Be sure to connect the DC reactor
Main circuit terminal
supplied with the 75K or more.
Control circuit terminal
When a DC reactor is connected to
the 55K or less, remove the jumper
across P1-P/+.
Three-phase AC
power supply
*2. To supply power to the
control circuit separately,
remove the jumper across
R1/L11 and S1/L21.
Control input signals (No voltage input allowed)
Terminal functions vary with
the input terminal
assignment (Pr. 178 to Pr. 189)
(Refer to the Instruction
Manual (applied))
holding selection
Multi-speed
selection
*3. JOG terminal can be used
as pulse train input terminal.
Use Pr.291 to select
JOG/pulse.
Second function selection
*4. AU terminal can be
used as PTC input
terminal.
Terminal 4 input selection
(Current input selection)
Selection of automatic restart
after instantaneous
power failure
Contact input common
(Common for external power supply transistor)
Frequency setting signal (Analog)
Frequency setting
potentiometer
1/2W1k Ω
*6
* 5. Terminal input specifications
can be changed by analog
input specifications
Auxiliary
switchover (Pr. 73, Pr. 267).
input
Note that the current at
terminal 2 and 4 is always 4
Terminal
to 20mA when the
4 input
voltage/current input switch is
(Current
set to ON. (A voltage/current
input)
input switch is provided for
the 5.5K or more.)
(Refer to the Instruction
Manual (applied))
*6 . It is recommended to use 2W1kΩ
when the frequency setting signal
is changed frequently.
CAUTION
· To prevent a malfunction due to noise, keep the signal cables more than 10cm away from the power cables.
· After wiring, wire offcuts must not be left in the inverter.
Wire offcuts can cause an alarm, failure or malfunction. Always keep the inverter clean.
When drilling mounting holes in an enclosure etc., take care not to allow chips and other foreign matter to enter the inverter.
8
Earth
(Ground)
MC
MCCB
R/L1
S/L2
T/L3
R1/L11
Jumper
S1/L21
*2
Earth
(Ground)
Forward
STF
rotation
start
STR
Reverse
rotation
start
STOP
Start self-
RH
High speed
RM
Middle
speed
RL
Low speed
JOG
Jog mode
RT
MRS
Output stop
RES
Reset
AU
CS
SD
PC
24VDC power supply
10E(+10V)
10(+5V)
3
2
2
5
1
(+)
1
(-)
(+)
4
(-)
Connector
for plug-in option
connection
Brake unit
*1
(Option)
R
*8
Jumper
Jumper
Jumper
P1
P/+
PX
PR
R
ON
EMC filter
ON/OFF
OFF
connecter
*9

Main circuit

Control circuit

*3
*4
AU
PTC
PU
connector
*5
Voltage/current
input switch
4 2
ON
USB
OFF
connector
0 to 5VDC
(Initial value)
0 to 10VDC
selected
*5
4 to 20mADC
(Analog common)
0 to ± 10VDC
(Initial value)
selected
0 to ± 5VDC
*5
4 to 20mADC
(Initial value)
0 to 5VDC
*5
selected
0 to 10VDC
Option connector 1
Option connector 2
Option connector 3
Terminating
resistor
*7. A CN8 connector is provided with the 75K
or more.
*8. Brake resistor (FR-ABR)
Remove the jumper across terminal PR-PX
when connecting a brake resistor.
(0.4K to 7.5K)
CN8
N/-
Terminal PR is provided for the 0.4K to 22K.
*7
Install a thermal relay to prevent an overheat
and burnout of the brake resistor.
(Refer to page 37)
U
V
W
*9.The FR-A720-0.4K and 0.75K
are not provided with the EMC
filter ON/OFF connector. (Always on)
C1
Terminal functions
B1
Relay output 1
vary with the output
(Alarm output)
terminal assignment
A1
(Pr. 195, Pr. 196)
(Refer to the
C2
Instruction Manual
(applied))
B2
Relay output 2
A2
Open collector output
RUN
Running
Terminal functions
SU
vary with the output
Up to frequency
terminal assignment
IPF
Instantaneous
(Pr. 190 to Pr. 194)
power failure
(Refer to the
OL
Instruction Manual
Overload
(applied))
FU
Frequency detection
SE
Open collector output common
Sink / source common
* 10. It is not necessary
when calibrating the
indicator from the
operation panel.
+
-
FM
*11
Calibration
resistor * 10
SD
AM
(+)
Analog signal output
(0 to 10VDC)
5
(-)
RS-485 terminals
TXD+
Data transmission
TXD-
RXD+
Data reception
RXD-
SG
GND
VCC
(Permissible load
5V
current 100mA)
Motor
IM
Earth (Ground)
Relay output
*11. FM terminal can
be used for pulse
train output of open
collector output
using Pr.291.
Indicator
(Frequency meter, etc.)
Moving-coil type
1mA full-scale

Advertisement

Table of Contents
loading

Table of Contents