Parameter List
Parameter
Commercial power-
supply switchover
135
sequence output
terminal selection
MC switchover
136
interlock time
137
Start waiting time
Commercial power-
supply operation
138
switchover
selection at an
alarm
Automatic
switchover
frequency between
139
inverter and
commercial power-
supply operation
Automatic
switchover ON
range between
159
commercial power-
supply and inverter
operation
140
143
to
Refer to Pr. 29.
144
Refer to Pr. 37.
PU display
145
language selection
148,149
Refer to Pr. 22.
108
Incre
Initial
Name
ments
Value
1
0
0.1s
1s
0.1s
0.5s
1
0
0.01Hz
9999
0.01Hz
9999
1
0
Range
Description
With commercial power-supply switchover
0
sequence
Without commercial power-supply
1
switchover sequence
Set the operation interlock time of MC2
0 to 100s
and MC3.
Set the time slightly longer (0.3 to 0.5s or
0 to 100s
so) than the time from when the ON signal
enters MC3 until it actually turns on.
Inverter output is stopped (motor coast) at
0
inverter fault.
Operation is automatically switched to the
commercial power-supply operation at
1
inverter fault (Not switched when an
external thermal error occurs)
Set the frequency to switch the inverter
0 to 60Hz
operation to the commercial power-supply
operation.
9999
Without automatic switchover
Valid during automatic switchover
operation (Pr. 139 ≠ 9999)
When the frequency command decreases
below (Pr. 139 - Pr. 159) after operation is
switched from inverter operation to
commercial power-supply operation, the
0 to 10Hz
inverter automatically switches operation
to the inverter operation and operates at
the frequency of frequency command.
When the inverter start command (STF/
STR) is turned off, operation is switched to
the inverter operation also.
Valid during automatic switchover
operation (Pr. 139 ≠ 9999)
When the inverter start command (STF/
STR) is turned off after operation is
9999
switched from the inverter operation to
commercial power-supply inverter
operation, operation is switched to the
inverter operation and the motor
decelerates to stop.
0
Japanese
1
English
2
Germany
3
French
4
Spanish
5
Italian
6
Swedish
7
Finnish
All
Param
Param
param
eter
eter
eter
copy
clear
clear
: enabled
× : disabled
×
×