METERING
7.4.5.3 Ambient Temperature by Monthly Averages
7.4.6
Analog outputs
7–14
Table 7–1: Measured RTD temperature
RTD type
Ω
100
Platinum
resistance
120 Ω Nickel
86.17
120.0
157.74
200.64
248.95
303.46
366.53
100 Ω Nickel
71.81
100.00
131.45
167.20
207.45
252.88
305.44
If the ambient temperature is entered as 12 monthly averages, program
the value for the month during which the relay is being commissioned.
Examine the
TEMPERATURE
Verify that values entered for other months do not affect the value for
the present month.
The analog output settings are located in the
setpoints section.
Connect a milliammeter to the analog output contacts: COM on A5 and
analog output 1 on A6, analog output 2 on A7, analog output 3 on A8,
analog output 4 on A9, analog output 5 on A10, analog output 6 on A11,
or analog output 7 on A12.
From the settings used for the tested analog output, determine the mA
range for the output and the driving signal and its range for the full
range of output current.
Apply the input signal and vary its amplitude over the full range and
ensure the analog output current is the correct amplitude.
Record the results in the table below.
Duplicate as required for each analog output.
CHAPTER 7: COMMISSIONING
Expected RTD reading
°C
°F
–50
–58
0
32
50
122
100
212
150
302
200
392
250
482
–50
–58
0
32
50
122
100
212
150
302
200
392
250
482
A2 METERING
AMBIENT TEMP
actual value to verify the programmed temperature.
S2 SYSTEM SETUP
745 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Measured RTD temperature
____°C ____°F (select one)
AMBIENT
ANALOG OUTPUTS