5.6.11.3 Volts per Hertz
VOLTS PER
HERTZ 1
745 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
PATH: SETPOINTS

[
]
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The volts per hertz element uses the ratio of the actual measured voltage at the voltage
terminal and the measured system frequency. For example, a measured phases-to-phase
voltage of 120 volts at 60 Hz, results in a ratio of 2 V/Hz. For 115% overload, the setting of
the volts per hertz minimum pickup would be 2.3 V/Hz.
The element has a linear reset characteristic. The reset time can be programmed to match
the cooling characteristic of the protected equipment. The element will fully reset after the
VOLTS-PER-HERTZ RESET
instantaneous element with no intentional delay, as a definite time element, or as an
inverse timed element.
MINIMUM OPERATING VOLTAGE: Enter the minimum value of voltage (in terms of
nominal VT secondary voltage) required to allow the volts per hertz 1 element to
operate.
VOLTS-PER-HERTZ 1 PICKUP: Enter the volts per hertz value (in V/Hz) above which the
volts per hertz 1 element will pickup and start the delay timer.
VOLTS-PER-HERTZ 1 SHAPE: Select the curve shape to be used for the volts per hertz 1
element. The inverse volts per hertz curve shapes are shown below.
VOLTS-PER-HERTZ 1 DELAY: Enter the time that the volts per hertz value must remain
above the pickup level before the element operates.
VOLTS-PER-HERTZ 1 RESET: Enter the time that the volts per hertz value must remain
below the pickup level before the element resets.
The curve for the inverse curve 1 shape is derived from the formula:
S4 ELEMENTS
OVEREXCITATION

VOLTS-PER-HERTZ 1
FUNCTION: Disabled
VOLTS-PER-HERTZ
RLYS (1-8): --------
VOLTS-PER-HERTZ 1
TARGET: Self-Reset
MINIMUM OPERATING
VOLTAGE: 0.10 x VT
VOLTS-PER-HERTZ 1
PICKUP: 2.36 V/Hz
VOLTS-PER-HERTZ 1
SHAPE: Definite Time
VOLTS-PER-HERTZ 1
DELAY: 2.00 s
VOLTS-PER-HERTZ 1
RESET: 0.0 s
VOLTS-PER-HERTZ 1
BLOCK: Disabled
value. The volts per hertz function can be used as an
D
--------------------------------- -
T
when
=
2
V F ⁄
--------------- -
1
Pickup
S4 ELEMENTS
VOLTS PER HERTZ 1(2)

Range:
Enabled, Disabled
Range:
1 to 8
Range:
Self-Reset, Latched, None
Range:
0.10 to 0.99 x VT in steps of
0.01
Range:
1.00 to 4.00 V/Hz in steps of
0.01
Range:
Definite Time, Inv Curve 1, Inv
Curve 2, Inv Curve 3
Range:
0.00 to 600.00 s in steps of 0.01
Range:
0.0 to 6000.0 s in steps of 0.1
Range:
Logc Inpt 1 to 16, Virt Inpt 1 to
16, Output Rly 2 to 8, SelfTest
Rly, Vir Outpt 1 to 5, Disabled
V
-- -
>
Pickup
F
(EQ 5.12)
5–85