GE 745 Instruction Manual page 222

Transformer protection system
Hide thumbs Also See for 745:
Table of Contents

Advertisement

A2 METERING
6.3.6.3 Current Demand
 W1 CURRENT
DEMAND
6.3.7
Ambient Temperature
 AMBIENT
TEMPERATURE
6.3.8
Loss of Life
 LOSS OF LIFE [
6–14
PATH: ACTUAL VALUES

[
]
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The current demand for winding 1 phases A through C are displayed in these messages.
The maximum current demand, the phase in which it occurred, and the date and time it
occurred are also shown. If the date has never been programmed, the default values
shown above appear. These messages are repeated for windings 2 and 3.
PATH: ACTUAL VALUES

[
]
Ambient temperature is monitored via an RTD connected to the 745.
PATH: ACTUAL VALUES

]
MESSAGE
MESSAGE
The
HOTTEST-SPOT WINDING TEMPERATURE
and the highest-load winding current. The
the hottest-spot temperature. The
equivalent service hours of the transformer.
A2 METERING
DEMAND

W1 PHASE A CURRENT
DEMAND: 0 A
W1 PHASE B CURRENT
DEMAND: 0 A
W1 PHASE C CURRENT
DEMAND: 0 A
MAXIMUM W1 DEMAND:
0 A in phase A
MAXIMUM W1 DEMAND
DATE: Jan 01 1996
MAXIMUM W1 DEMAND
TIME: 00:00:00.000
A2 METERING
AMBIENT TEMPERATURE

AMBIENT TEMPERATURE:
0°C
A2 METERING
LOSS OF LIFE

HOTTEST-SPOT WINDING
TEMPERATURE: 1°C
INSULATION AGING
FACTOR:
0.0
TOTAL ACCUM LOSS OF
LIFE: 0.00 hours
is calculated from the ambient temperature
INSULATION AGING FACTOR
TOTAL ACCUM LOSS OF LIFE
745 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 6: ACTUAL VALUES
W1(3) CURRENT DEMAND

is calculated from
value displays the total

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents