S4 ELEMENTS
5.6.16 Transformer Overload
XFORMER
OVERLOAD
5–96
FIGURE 5–44: Current demand scheme logic
PATH: SETPOINTS

[]
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
TRANSFORMER OVERLOAD PICKUP: This setting identifies the level of transformer
overload, where the pickup delay starts timing. The setting is expressed as a
percentage of the transformer base MVA rating, and is normally set at or above the
maximum rated MVA from the transformer nameplate.
XFMR OVERTEMP ALARM SIGNAL: Select any logic input that, when asserted,
indicates the transformer cooling system has failed and an over-temperature
condition exists. The logic input should be connected to the transformer winding
temperature alarm contacts.
S4 ELEMENTS
XFORMER OVERLOAD

TRANSFORMER OVERLOAD
FUNCTION: Disabled
TRANSFORMER OVERLOAD
RLYS (1-8): --------
TRANSFORMER OVERLOAD
TARGET: Self-Reset
TRANSFORMER OVERLOAD
PICKUP: 208% rated
TRANSFORMER OVERLOAD
DELAY: 10 s
TRANSFORMER OVERLOAD
BLOCK: Disabled
XFMR OVERTEMP ALARM
SIGNAL: Disabled
745 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETPOINTS
Range:
Enabled, Disabled
Range:
1 to 8
Range:
Self-Reset, Latched, None
Range:
50 to 300% of Rated Load in
steps of 1
Range:
0 to 60000 s in steps of 1
Range:
Logc Inpt 1 to 16, Virt Inpt 1 to
16, Output Rly 2 to 8, SelfTest
Rly, Vir Outpt 1 to 5, Disabled
Range:
Disabled, Logc Inpt 1 to 16