4 Faults and alarms
4.2 List of faults and alarms
A07480
EPOS: Software limit switch plus reached
Message value:
-
Message class:
Application / technological function faulted (17)
Drive object:
VECTOR_G
Reaction:
NONE
Acknowledge:
NONE
Cause:
The axis is at the position of the software limit switch plus. An active traversing block was interrupted.
Remedy:
- correct the target position.
- change software limit switch plus (CI: p2579, p2581).
F07481 (A)
EPOS: Axis position < software limit switch minus
Message value:
-
Message class:
Application / technological function faulted (17)
Drive object:
VECTOR_G
Reaction:
OFF1 (OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
The actual position of the axis is less than the position of the software limit switch minus.
Remedy:
- correct the target position.
- change software limit switch minus (CI: p2578, p2580).
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F07482 (A)
EPOS: Axis position > software limit switch plus
Message value:
-
Message class:
Application / technological function faulted (17)
Drive object:
VECTOR_G
Reaction:
OFF1 (OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
The actual position of the axis is greater than the position of the software limit switch plus.
Remedy:
- correct the target position.
- change software limit switch plus (CI: p2579, p2581).
Reaction upon A:
NONE
Acknowl. upon A:
NONE
A07483
EPOS: Travel to fixed stop clamping torque not reached
Message value:
-
Message class:
Application / technological function faulted (17)
Drive object:
VECTOR_G
Reaction:
NONE
Acknowledge:
NONE
Cause:
The fixed stop in the traversing block was reached without the clamping torque/clamping force having been achieved.
Remedy:
- Check the maximum torque-generating current (r1533).
- check the torque limits (p1520, p1521).
- check the power limits (p1530, p1531).
- check the BICO interconnections of the torque limits (p1522, p1523, p1528, p1529).
F07484
EPOS: Fixed stop outside the monitoring window
Message value:
-
Message class:
Application / technological function faulted (17)
Drive object:
VECTOR_G
Reaction:
OFF3 (OFF1, OFF2)
Acknowledge:
IMMEDIATELY
Cause:
In the "fixed stop reached" state, the axis has moved outside the defined monitoring window (p2635).
Remedy:
- check the monitoring window (p2635).
- check the mechanical system.
1456