Temperature
Specifications
(Continuous
Operation)
Temperature
10 °C to 35 °C (50 °F to 95 °F) with no direct sunlight on the equipment.
Ranges (for
altitude less than
950 m or 3117 ft)
Humidity
10% to 80% Relative Humidity with 26 °C (78.8 °F) maximum dew point.
Percentage Range
Maximum
Specifications
vibration
Operating
0.26 G
Storage
1.87 G
Maximum
Specifications
shock
Operating
One shock pulse in the positive z axis of 31 G for 2.6 ms in all operational
orientations.
Storage
Six consecutively executed shock pulses in the positive and negative x, y, and z
axes (one pulse on each side of the system) of 71 G for up to 2 ms.
Maximum
Specifications
altitude
Operating
3,048 m (10,000 ft)
Storage
12,000 m (39,370 ft).
Operating
Specifications
temperature
de-rating
Up to 35 °C (95 °F) Maximum temperature is reduced by 1 °C/300 m (1 °F/547 ft) above 950 m (3,117
ft).
35 °C to 40 °C (95
Maximum temperature is reduced by 1 °C/175 m (1 °F/319 ft) above 950 m (3,117 ft).
°F to 104 °F)
40 °C to 45 °C
Maximum temperature is reduced by 1 °C/125 m (1 °F/228 ft) above 950 m (3,117
(104 °F to 113 °F)
ft).
The following section defines the limits to help avoid IT equipment damage and/or failure from
particulates and gaseous contamination. If the levels of particulates or gaseous pollution are beyond the
specified limits and cause equipment damage or failure, you may need to rectify the environmental
conditions. Remediation of environmental conditions is the responsibility of the customer.
94
at 5 Hz to 350 Hz (all operation orientations).
rms
at 10 Hz to 500 Hz for 15 min (all six sides tested).
rms