3) Insert the wire into a socket.
Note
When using a stranded wire without a blade terminal, twist enough to avoid short circuit with a nearby terminals or
wires.
Place the flathead screwdriver vertical to the open/close button. In case the blade tip slips, it may cause damage of
inverter or injury.
Wire removal
Pull the wire with pushing the open/close button all the
way down firmly with a flathead screwdriver.
Open/close button
(3)
Wiring instructions
1) Terminals SD, SE and 5 are common to the I/O signals. Do not earth (ground) them.
2) It is recommended to use the cables of 0.3mm
3) The maximum wiring length should be 30m (98.43feet).
4) Do not short across terminals PC and SD. Inverter may be damaged.
5) Use two or more parallel micro-signal contacts or twin contacts to prevent
contact faults when using contact inputs since the control circuit input signals
are micro-currents.
6) Use shielded or twisted cables for connection to the control circuit terminals and run them away from the main and power
circuits (including the 200V relay sequence circuit).
7) Do not apply a voltage to the contact input terminals (e.g. STF) of the control circuit.
8) Always apply a voltage to the fault output terminals (A, B, C) via a relay coil, lamp, etc.
When using a single wire or stranded wire without a blade terminal, push an open/
close button all the way down with a flathead screw driver, and insert the wire.
Flathead screwdriver
2
2
to 0.75mm
gauge for connection to the control circuit terminals.
Open/close button
Note
Pulling out the terminal block forcefully without pushing
the open/close button all the way down may damage the
terminal block.
Use a small flathead screwdriver (Tip thickness: 0.4mm
(0.02 inch)/tip width: 2.5mm (0.10 inch)).
If a flathead screwdriver with a narrow tip is used,
terminal block may be damaged.
Introduced products :(as of Oct. 2008)
Product
Type
Flathead
SZF 0- 0,4 x 2,5
screwdriver
Place the flathead screwdriver vertical to the open/close
button. In case the blade tip slips, it may cause to
damage of inverter or injury.