Mitsubishi Electric FR-D720-008 Installation Manuallines page 11

Hide thumbs Also See for FR-D720-008:
Table of Contents

Advertisement

WIRING
NOTE
Tighten the terminal screw to the specified torque. A screw that has been tighten too loosely can cause a short circuit or
malfunction. A screw that has been tighten too tightly can cause a short circuit or malfunction due to the unit breakage.
Use crimping terminals with insulation sleeve to wire the power supply and motor.
The line voltage drop can be calculated by the following formula:
3 × wire resistance[mΩ/m] × wiring distance[m] × current[A]
Line voltage drop [V]=
Use a larger diameter cable when the wiring distance is long or when it is desired to decrease the voltage drop (torque
reduction) in the low speed range.
8
1000

Hide quick links: