Supplying Power To The M-Net Transmission Lines - Mitsubishi Electric GB-50ADA-A Installation Instructions Manual

Hide thumbs Also See for GB-50ADA-A:
Table of Contents

Advertisement

3-3. Supplying power to the M-NET transmission lines

GB-50ADA has a built-in function to supply power to the M-NET transmission line. (power supply coefficient: 6)
The total power consumption coefficient of the system controller and M-NET remote controller to which GB-50ADA supplies
power (See table 1) should not exceed the power supply coefficient of GB-50ADA, which is six.
Table 1 Power consumption coefficient of the controller
System controller
ON/OFF remote controller
1
Table 2 No. of connectable units
System controller
ON/OFF remote controller
6 units
Table 3 No. of connectable units in systems with various combinations of remote controllers
Total number of system remote controllers,
schedule timers, and group remote
controllers combined.
Note
When connecting both GB-50ADA and BAC-HD150 (BM ADAPTER) to the same M-NET system, certain
restrictions apply.
Consult your dealer for details.
System remote controller
Schedule timer
Group remote controller
0.5
System remote controller
Schedule timer
Group remote controller
12 units
0
1
2
3
4
5
6
7
8
9
10
11
12
- 8 -
M-NET remote controller
ME remote controller
LOSSNAY remote controller
0.25
M-NET remote controller
ME remote controller
LOSSNAY remote controller
24 units
Total number of ON/OFF remote controllers
0
1
2
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V: connectable
3
4
5
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
6
V

Hide quick links: