GGIO class
Attribute Name
Attr. Type Explanation
LNName
Data
Common Logical Node Information
EEHealth
INS
EEName
DPL
Loc
SPS
OpCntRs
INC
Measured values
AnIn
MV
Controls
SPCSO
SPC
DPCSO
DPC
ISCSO
INC
Status Information
IntIn
INS
Alm
SPS
Ind01
SPS
Ind02
SPS
Ind16
SPS
Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
LN shall inherit all Mandatory Data from Common Logical Node Class
External equipment health (external sensor)
External equipment name plate
Local operation
Resetable operation counter
Analogue input
Single point controllable status output
Double point controllable status output
Integer status controllable status output
Integer status input
General single alarm
General indication (binary input)
General indication (binary input)
General indication (binary input)
- 758 -
6F2S1931 (0.20)
(MICS Ed.1)
T M/O GRB200
M
O
N
O
N
O
N
O
N
O
N
O
N
O
N
O
N
O
N
O
N
O
Y
O
Y
O
Y
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)