Supervision of binary IO modules (BIO error)
9.2.19
Supervision function is provided for detecting the operation failures of binary IO modules (BIO)
in MainUnit, SubUnit#1, and SubUnit#2†.
†Note: The function can operate for respective BIO modules mounted in the IED; the user
should have settings in them, which are located at the IO slot identified with the
number.
Error level
(i)
The default error level has been set at level 1 (Serious error
level arbitrarily. For example, the user can program the level using setting [CHK_BIO1:Lvl]
when the BIO module at the IO#1
setting [CHK_BIO1:Sw]. Similarly the user can program the level using settings
[CHK_S1BIO1:Lvl] and [CHK_S1BIO1:Sw] when BIO#1 in SubUnit#1 is required. The
manufacturer sets one (1) second to detect the failure; it is reset with in a second when the
failure is cleared.
Note: When the error is detected, the entire operation of the IED is stopped forcibly.
1
Note: The location of the VCT slot is discussed in Chapter
2
case and module slot
Error message
(ii)
When detecting an error, an error message can be shown on the LCD screen and an LED is lit.
Table 9.2-38 Messages for MainUnit provided by the supervisor in CHK_BIO
Message and level
BIO#1 error
BIO#2 error
BIO#3 error
BIO#4 error
BIO#5 error
BIO#6 error
BIO#7 error
BIO#8 error
Error level
slot should be supervised in MainUnit; then, set On for the
2
.
Meaning of the information
Detection of the BIO failure at IO slot#1 in MainUnit
Detection of the BIO failure at IO slot#2 in MainUnit
Detection of the BIO failure at IO slot#3 in MainUnit
Detection of the BIO failure at IO slot#4 in MainUnit
Detection of the BIO failure at IO slot#5 in MainUnit
Detection of the BIO failure at IO slot#6 in MainUnit
Detection of the BIO failure at IO slot#7 in MainUnit
Detection of the BIO failure at IO slot#8 in MainUnit
Serious error (Level 1)
- 487 -
6F2S1931 (0.20)
), but the user can set the error
1
Technical description: IED
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)