IEC 61850 communication
Figure 10.3-1 shows a substation automation system (SAS) and a number of IEDs connected
via a Ring LAN (100BASE-FX). The IEDs can have communication with other devices using
the international standard protocol (IEC 61850 standard‡); additionally, the ring network
topology is used to achieve network redundancy in the system. The user should use the GR-
TIEMS to configure the protocol in the IEC 61850 standard. That is, the functions for the
protection, the measurement, monitoring at local and remote, controlling and logging the data
are required to program in the IEC 61850 standard.
GPS
Operator
Workstation
SNTP
Ethernet LAN (TCP/IP)
Fiber Optic Ring: 100BASE-FX
GBU GRT GRG
GBU GRL GRB
Figure 10.3-1 SAS network using IEC 61850 protocol
†Note: When applying IEC 61850 communications, the user should map application
signals with the required logical-nodes (LNs) within the IED. In this manual, we
show the application signals as Data IDs; hence, the user is able to connect the
Data IDs with the required LNs using the engineering tool (GR-TIEMS) provided
by Toshiba. For the GR-TIEMS, see Chapter
‡Note: Before using the IEC 61850 communications feature provided within the IED, the
user should verify its IEC 61850 capability by reviewing both the protocol-
implementation-conformance-statement (PICS) and the model-implementation-
Engineering
Printer
Workstation
GBU GRG GRZ
GOOSE
- 535 -
Remote
Monitoring
Communication
Network
Router/
Modem
CONTROL
MEASUREMENT
GBU GRT GRL
Engineering tool
.
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)
6F2S1931 (0.20)
Substation
Computer