2.2 List of parameters
p0860

BI: Line contactor feedback signal / Line contact feedb

B_INF, VECTOR_G
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: Commands
Not for motor type: -
Min
-
Description:
Sets the signal source for the feedback signal from the line contactor.
Recommend.:
When the monitoring is activated (BI: p0860 not equal to r0863.1), then to control the line contactor, signal BO:
r0863.1 of its own drive object should be used.
Dependency:
Refer to: p0861, r0863
Notice:
The line contactor monitoring is de-activated if the control signal of the particular drive object is set as the signal
source for the feedback signal of the line contactor (BI: p0860 = r0863.1).
Note:
The state of the line contactor is monitored depending on signal BO: r0863.1.
When the monitoring is activated (BI: p0860 not equal to r0863.1), fault F07300 is then also output if the contactor is
closed before it is controlled using r0863.1.
p0861

Line contactor monitoring time / LineContact t_mon

B_INF, VECTOR_G
Can be changed: T
Data type: FloatingPoint32
P-Group: Commands
Not for motor type: -
Min
0 [ms]
Description:
Sets the monitoring time of the line contactor.
This time starts each time that the line contactor switches (r0863.1). If a feedback signal is not received from the line
contactor within the time, a message is output.
Dependency:
Refer to: p0860, r0863
Note:
The monitoring function is disabled for the factory setting of p0860.
p0862

Power unit ON delay / PU t_on

B_INF, VECTOR_G
Can be changed: T
Data type: FloatingPoint32
P-Group: Commands
Not for motor type: -
Min
0 [ms]
Description:
Sets the delay time for the control command of the power unit and a line contactor, if used.
Note:
This means that it is possible to realize a shifted (delayed) pre-charging or power-on using a single ON command.
When the infeed units are active, before the line contactor is closed, an offset adjustment of the current measurement
is carried out for a duration of 120 ms (p3491).
r0863.0...2

CO/BO: Drive coupling status word/control word / CoupleZSW/STW

B_INF, VECTOR_G
Can be changed: -
Data type: Unsigned16
P-Group: Commands
Not for motor type: -
Min
-
Description:
Display and BICO output for the status word and control word of the drive coupling.
262
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
5000 [ms]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
65000 [ms]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
List Manual (LH2), 04/2014, A5E03263479A
Access level: 3
Func. diagram: 2634, 8734,
8834, 8934
Unit selection: -
Expert list: 1
Factory setting
863.1
Access level: 2
Func. diagram: 2634, 8734,
8834, 8934
Unit selection: -
Expert list: 1
Factory setting
100 [ms]
Access level: 3
Func. diagram: 2610, 8732,
8832, 8932
Unit selection: -
Expert list: 1
Factory setting
0 [ms]
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
SINAMICS G130/G150