Honeywell Perfect Window HR150 Product Data page 5

Fresh air ventilation systems
Hide thumbs Also See for Perfect Window HR150:
Table of Contents

Advertisement

SEAL OUTER LINING OF FLEX
DUCT TO OUTER COLLAR
INSULATED
FLEX DUCT
SEAL INTERIOR LINING OF
FLEX DUCT TO INSIDE COLLAR
Fig. 5. Sealing insulated duct terminations.
Design and installation of ductwork must be according to
standard HVAC practice to deliver required quantities of fresh
air to temperature-controlled space and exhaust equivalent
quantities of room air to the outside.
Keep intake and exhaust duct runs as short as possible with
few bends or elbows.
• Keep duct sizes as large as possible throughout the
installation.
• Use a 6 in. diameter round duct for all connections to and
from the ventilator.
• Separate outside intake and exhaust vents by at least
6 ft (2m).
OUTDOORS
EXHAUST AIR FROM
VARIOUS PARTS OF
HOME (BATHROOMS
IF REQUIRED; KITCHENS
IF REQUIRED; ROOMS
WITHOUT OPERABLE WINDOWS,
AND POTENTIALLY BASEMENTS).
NOTES:
1.
FURNACE BLOWER NEED NOT OPERATE TO PROVIDE GOOD AIR DISTRIBUTION/QUALITY WITH THIS SYSTEM.
2.
IF FURNACE BLOWER OPERATION IS REQUIRED TO HELP DISTRIBUTE SUPPLY AIR: RUN CONTINUOUSLY
OR INTERLINK ELECTRICALLY (LOW VOLTAGE).
3.
NO SEPARATION REQUIREMENTS ARE NECESSARY BETWEEN DIRECT CONNECTION POINT AND FURNACE.
4.
WEATHER-HOOD ARRANGEMENT IS FOR DRAWING ONLY. 6 FT (2m) MINIMUM SEPARATION REQUIRED,
18 IN. (0.46m) ABOVE GRADE MINIMUM.
Fig. 6. Direct connection of supply air stream to furnace cold air return for HRV/ERV.
HR150, 200; ER150, 200 PERFECT WINDOW™ FRESH AIR VENTILATION SYSTEMS
NOTES:
COLLAR ON
• Ducting the supply outlet and/or the exhaust inlet of the
VENTILATOR
M6557
NOTE: When the home is occupied, continuous operation of
• An electrical interlock or an automatically powered damper
5
Do not locate the fresh air vent where it blows
directly onto occupants or the thermostat.
Do not locate the fresh air intake close to known
sources of pollutants such as automobile exhaust,
a dryer vent or chimney smoke.
ventilator to the return air plenum of the air handler is an
excellent way to distribute fresh air and exhaust stale air
from all parts of the house, while reducing installation costs.
When choosing this method, balance the ventilator when
the air handler is running and interlock the ventilator so that
it can run only when the air handler runs. See Fig. 6. An
alternate method is to balance the ventilator when the air
handler is not running and let the ventilator run whether the
air handler is running or not, see Fig. 7. An independent
installation is shown in Fig. 8.
the ventilator is recommended. When the furnace air
handler operates, fresh air is distributed through the
heating/air conditioning supply registers. When the air
handler is off, fresh air is delivered through both sup-
plies and returns.
must be used to prevent unwanted entry of outside air if the
ventilator is turned off while the furnace air handler
continues to operate.
RETURN
AIR
COLD AIR
RETURN
FORCED AIR
FURNACE
COMBUSTION
OR ELECTRIC
M6549D
68-0171—10

Advertisement

Table of Contents
loading

Table of Contents