Honeywell Perfect Window HR150 200 Product Data

Perfect window fresh air ventilation systems

Advertisement

HR150, 200; ER150, 200 Perfect Window™
Fresh Air Ventilation Systems
Included In thIs VentIlatIon system Box
Tools and accessories needed to install Perfect
Window™ Fresh Air Ventilation Systems
Wire cutter/stripper
18-gauge wire (up to 5 conductor)
Standard screwdriver
Insulated 6-inch round duct
Non-insulated 6-inch round duct
Two 6-inch weather hoods
Two 6-inch starter collars
1/2-inch I.D. drain hose
Airflow balancing kit
Foil tape
M29857
F
F
1
2
F
F
4
5
OPTIONAL CONTROLS SOLD SEPARATELY
HR150/200 or ER150/200 Perfect
Window™ Fresh Air Ventilation System
Owner's Manual
Hanging straps
* T-fitting
* 2 drain spouts
e
VisionPRO IAQ control
F
1
TrueIAQ
F
2
Dehumidistat H8908
F
3
Digital fan timer
F
4
W8150 ventilation control
F
5
*
Not with "C" models.
PRODUCT DATA
*
*
e
F
3
68-0171-12

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell Perfect Window HR150 200

  • Page 1 HR150, 200; ER150, 200 Perfect Window™ Fresh Air Ventilation Systems PRODUCT DATA Included In thIs VentIlatIon system Box M29857 OPTIONAL CONTROLS SOLD SEPARATELY Tools and accessories needed to install Perfect HR150/200 or ER150/200 Perfect Window™ Fresh Air Ventilation Systems Window™ Fresh Air Ventilation System Wire cutter/stripper Owner’s Manual 18-gauge wire (up to 5 conductor)
  • Page 3: Table Of Contents

    NEED HELP? For assistance with this product please visit http://yourhome.honeywell.com or call Honeywell Customer Care toll-free at 1-800-468-1502. Read and save these instructions. ® U.S. Registered Trademark. Patents pending. Copyright © 2009 Honeywell International Inc. All rights reserved. HR150, 200; ER150, 200 Perfect Window™ Fresh Air Ventilation Systems 68-0171—12...
  • Page 4: Safety Definitions And Precautions

    Safety Definitions and Precautions Safety Definitions These safety terms identify information you must read. CAUTION: Indicates a hazardous situation which, if not avoided, could cause bodily injury or property damage. WARNING: Indicates a hazardous situation which, if not avoided, could result in death or serious injury. Safety Precautions Make sure you read and understand the following safety and/or property hazards before installing, using, or working with the Perfect Window™...
  • Page 5: Application

    Application The HR150B and HR200B Perfect Window™ Fresh Air Ventilation Systems provide proper levels of ventilation with energy savings by transferring heat between the exhaust and fresh air streams. The ER150B and ER200B Perfect Window™ Fresh Air Ventilation Systems provide proper levels of ventilation with energy savings by transferring heat and moisture between the exhaust and fresh air streams.
  • Page 6: Planning The Installation

    Planning the Installation Failure to comply with these requirements will result in voided warranty, improper installation, and service callbacks. FRESH AIR The Fresh Air Ventilation System is designed to FROM OUTSIDE supply fresh air and exhaust stale air. The system draws fresh outdoor air through the ventilator for STALE DEFROST...
  • Page 7: Sizing

    Exhaust air flow required = 150 cfm suggests the following: • 7.5 CFM per person (count people as 1 per Any Honeywell ventilation unit provides suitable bedroom plus 1) plus 1 CFM per 100 sq. ft. ventilation capacity. See Fig. 22. Example: 2200 sq.
  • Page 8: Mounting Position And Location

    Mounting Position and Location The HR150/ER150 and HR200/ER200 can be suspended from exposed ceiling joists, ceiling surface Install HR150/ER150 and HR200/ER200 in a or floor mounted. (Level ventilator so drains function conditioned space using these guidelines: correctly.) • Pipe drain line (ER150C and ER200C do not have drain kits) from the ventilator to a drain.
  • Page 9 Design and installation of ductwork must be according to standard HVAC practice to deliver required quantities of fresh air to temperature-controlled space and exhaust equivalent quantities of room air to the outside. Keep intake and exhaust duct runs as short as possible with few bends or elbows. •...
  • Page 10 RETURN 40 IN. (1m) MINIMUM OUTDOORS NOTES: FORCED AIR FURNACE BLOWER IS REQUIRED TO OPERATE WHEN VENTILATION IS REQUIRED. FURNACE SET THE FURNACE BLOWER TO RUN CONTINUOUSLY, OR INTERLINK ELECTRICALLY (LOW VOLTAGE). COMBUSTION OR ELECTRIC MINIMUM SEPARATION OF 40 IN. IS REQUIRED BETWEEN THE TWO COLD AIR DIRECT CONNECTIONS.
  • Page 11: Balancing Airflow

    Balancing Airflow Moisture Control When a building is new, there is excess moisture in Balancing the airflow verifies that the Fresh Air the wood, plaster, cement and other construction Ventilation System is delivering the intended airflow materials. When the new building is occupied, the and energy performance.
  • Page 12: Mounting

    INSTALLATION When Installing this Product… 1. Read these instructions carefully. Failure to follow these instructions could damage the product or cause a hazardous condition. 2. Check the ratings on the product to make sure the product is suitable for your application. 3.
  • Page 13: Installing Drain Line And P-Trap

    Installing Drain Line and P-Trap There are two holes at the bottom of the ventilator for the drain pan connectors. DRAIN O RING Insert the connectors through the hole in the drain pan and the bottom of the unit. Place the washer and nut on the connector. BOTTOM Hand tighten the nut.
  • Page 14: Wiring

    Heat Recovery Ventilator (HRV) and Energy Recovery Ventilator (ERV) Connections The connector is a three-prong, 120 Vac plug with ground. If further wiring is required, Honeywell recommends that a licensed electrician make all electrical connections. It is very important that the unit be correctly grounded.
  • Page 15 CONTROL OPTIONS VISIONPRO IAQ VNT1, 2 VNT HI TERMINALS TRUE IAQ VENT 12 15 TERMINALS W8150 DSTAT DSTAT TERMINALS MECHANICAL JUMPER BETWEEN VNT COM AND RED. TIMER DRY JUMPER BETWEEN VNT COM AND RED. CONTACTS M29838 CHOOSE AMONG AVAILABLE CONTROLS. ALL WIRE IDENTICALLY.
  • Page 16 FURNACE VisionPRO IAQ VNT HI DHM 1 DHM 2 VNT 1 VNT HI VNT 2 THERMOSTAT DSTAT DSTAT JUMPER BETWEEN VNT COM AND RED. JUMPER BETWEEN DHM2 AND VNT1. M29848 M29847 Fig. 16. Wiring VisionPRO IAQ for ventilation and Fig. 15. Wiring for fan interlock.
  • Page 17 LEGEND HIGH VOLTAGE 12V LOW VOLTAGE THERMISTOR VNT HI (NOT ON ALL UNITS) DSTAT BLUE BLACK GREEN WHITE LINE NEUTRAL FAN O/P AUTO- DEFROST TRANSFORMER DETAIL GREEN AUTO-TRANSFORMER DETAIL CAPACITOR PLUG-IN CONNECTOR DIRECT MOUNTED AUTO MOTOR CAPACITOR TRANSFORMER DEFROST DETAILS PCB PLUG-IN PCB PLUG-IN PLUG IN...
  • Page 18: Airflow Balancing

    Airflow Balancing Volume-balanced airflow in the ventilator is required. Volume of outside air brought in must equal the volume of air the unit exhausts. If airflow is not correctly balanced: • unit does not operate at its maximum efficiency. • negative or positive air pressure can occur in the house.
  • Page 19: Startup And Checkout

    For maximum efficiency, the Fresh Air Ventilation System must be maintained on a regular basis. Inspecting Exterior Hoods Honeywell recommends checking and cleaning at Inspect exterior hoods at least monthly. Be sure least twice a year, preferably at the beginning of each exhaust and fresh air supply hoods are not blocked heating and cooling season.
  • Page 20: Troublshooting

    TROUBLESHOOTING Table 1. Troubleshooting Guide. Symptom Cause Solution Poor airflow • Plugged outside hood 1/4 in. (6 mm) mesh. • Clean exterior hoods or vents • Filters plugged. • Remove and clean filter. • Core obstructed. • Remove and clean core. •...
  • Page 21 Symptom Cause Solution Humidity Dehumidistat is set too high. Set dehumidistat lower. levels are • Undersized ventilator to handle hot tub, indoor • Cover pools and hot tubs when not in use. too high; pool, etc. condensation • Lifestyle of occupants. •...
  • Page 22: Parts List

    PARTS LIST HR/ER Parts List Item Part Number for Description Number HR150B/ ER150B/ ER150C/ (Fig. 21) HR200B ER200B ER200C 209746 Heat Transfer Core, Aluminum with Plastic Frame 32002074-001 32002074-001 Cross-Flow Energy Transfer Core, with Guide Channels, diamond shape made before August 2005* 50048918-001 50048918-001 Universal Energy Transfer Core with guide channels to fit...
  • Page 23 M29855 Fig. 21. HR150/HR200 and ER150/ER200 exploded view of parts keyed to HR/ER Parts List. HR150, 200; ER150, 200 Perfect Window™ Fresh Air Ventilation Systems 68-0171—12...
  • Page 24: Specifications

    Specifications Mounting IMPORTANT Most models mount in conditioned space such as a The specifications given in this publication do basement, utility room, hallway or closet. Can also be not include normal manufacturing tolerances. mounted in conditioned attic space. Therefore, this unit might not exactly match the listed specifications.
  • Page 25 HIGH SPEED HIGH SPEED LOW SPEED LOW SPEED 1 STATIC PRESSURE (IN W.G.) STATIC PRESSURE (IN W.G.) MANUFACTURER’S DATA MANUFACTURER’S DATA HR150 VENTILATION PERFORMANCE (HV1) HR200 VENTILATION PERFORMANCE (HVI) EXT STATIC NET SUPPLY EXT STATIC NET SUPPLY PRESSURE AIR FLOW PRESSURE AIR FLOW (Pa)
  • Page 26 HIGH SPEED HIGH SPEED FLOW FLOW (CFM) LOW SPEED (CFM) LOW SPEED STATIC PRESSURE (IN. W.G.) STATIC PRESSURE (IN. W.G.) MANUFACTURER’S DATA. MANUFACTURER’S DATA. ER150 VENTILATION PERFORMANCE ER200 VENTILATION PERFORMANCE NET SUPPLY AT LOW IN CFM (L/s) AGAINST EXTERNAL STATIC PRESSURE NET SUPPLY AT LOW IN CFM (L/s) AGAINST EXTERNAL STATIC PRESSURE E.S.P.
  • Page 28 Automation and Control Solutions Honeywell International Inc. 1985 Douglas Drive North Golden Valley, MN 55422 Honeywell Limited–Honeywell Limitée 35 Dynamic Drive ® U.S. Registered Trademark Toronto, Ontario M1V 4Z9 © 2010 Honeywell International Inc. 68-0171—12 M.S. Rev. 02-10 http://yourhome.honeywell.com Printed in U.S.A.