Table 7 I/O Module Installation Limitations - Honeywell UMC800 Installation And User Manual

Honeywell umc800 controller installation and user guide
Hide thumbs Also See for UMC800:
Table of Contents

Advertisement

Mounting and Wiring
Plug-in Module Locations
I/O module limits
The controller backplane accommodates I/O module types, subject to the limitations as shown in Table 7.
Slot Locations identify the allowable locations in the controller for each I/O module type. Maximum
Allowed describes the maximum I/O configuration for each I/O type in a controller.
I/O Module Type
Universal Analog Input (ID: 1)
Analog Output (ID: 2)
Digital Input (ID: 3,4,5)
Digital Input 16 point (ID: B)
Digital Output (ID: 6,7,8)
Digital Output (ID: A)
± 15 Vdc pH Power Module (ID: C)
Pulse/Frequency Input (ID: D)
NOTE: Total combined I/O of all types is limited by the 16 available controller I/O slots.
* Total of 96 DI/DOs allowed for all types combined.
20

Table 7 I/O module installation limitations

Slot Locations
(See Figure 9)
1 through 16
1 through 10
1 through 16
14 through 16
1 through 8
9 through 16
5, 6
1 through 16
UMC800 Controller Installation and User Guide
Maximum Allowed
16 modules (64 points)
4 modules (16 points)
16 modules (96 points)*
3 modules (48 points)*
8 modules (48 points)*
2 modules (12 points)*
2 modules (8 points)
16 modules (64 points)