Specifications
I/O Module Configuration
Component
Analog Outputs
(Module ID 2)
Digital Inputs
94
Parameter
Accuracy (at reference
conditions)
A/D Converter
Resolution
Temperature Effect on
Accuracy
Long Term Stability
Number of Outputs
Isolation from Logic
Accuracy
Temperature Effects
D/A Resolution
Inputs per Module
Input Voltage Range
Peak Voltage
AC Frequency
ON Voltage Level
OFF Voltage Level
Input Impedance
Input Current
Minimum ON Current
Maximum OFF Current
Base Power Required *
OFF to ON Response
ON to OFF response
UMC800 Controller Installation and User Guide
Description
Factory configured accuracy = ± 0.1 % of range
Cold junction accuracy = ± 0.5 °C
Field calibration accuracy = ± 0.05 % of range
Reference conditions:
Temperature = 25 °C ± 3 °C (77 °F ± 5 °F)
Humidity = 10 % to 55 % RH non-condensing
Line voltage = Nominal ± 1 %
Source resistance = 0 ohm
Series mode and common mode = 0 V
Frequency = Nominal ± 1 %
Better than 1 part in 50,000 at 50 Hz.
Better than 1 part in 41,667 at 60 Hz.
0.15 % per 10 °C in the rated limits
0.1 % per year
4 per module (isolated), up to 4 modules per controller (16
outputs)
3.25 K Vac RMS
Factory configured accuracy = 0.1 % at reference conditions
Field calibration accuracy = 0.1 %
0.1 % per 10 °C in the rated limits
16 bits
AC Inputs
(Module ID 5)
6
80 Vac to 264 Vac
264 Vac
47 Hz to 63 Hz
75 Vac minimum
20 Vac maximum
12K @ 60 Hz
13 mA @ 100 Vac, 60 Hz
11 mA @ 100 Vac, 50 Hz
5 mA
2 mA
50 mA maximum
5 ms to 30 ms
10 ms to 50 ms
DC Inputs
(Module ID 4)
6 (sink/source)
10.2 Vdc to 26.4 Vdc
26.4 Vdc
N/A
9.5 Vdc minimum
3.5 Vdc maximum
2.7 K
4.0 mA @ 12 Vdc
8.5 mA @ 24 Vdc
3.5 mA
1.5 mA
50 mA maximum
1 ms to 8 ms
1 ms to 8 ms
Release F