Zigbee wireless survey toolkit for tb7200/tb7300/tb7600 series thermostats
Table of Contents

Advertisement

ZIGBEE WIRELESS SURVEY TOOLKIT FOR TB7200/TB7300/TB7600 SERIES THERMOSTATS
WIRELESS THERMOSTAT
7. Repeat steps 2-5 until you establish the maximum
range covered by 5 hops where the last position
recorded represents the safest furthest position that
can be covered by a single controller (Fig. 12) and
PROPOSED
LOCATION
WEBS
CONTROLLER
MAXIMUM LINEAR DISTANCE COVERED BY A SINGLE WEBS CONTROLLER.
If more than 5 hops could be required by any
device, we recommend adding another controller
with wireless communication card. (Fig. 13).
Please note that a hop in this case is defined as
the maximum linear connectivity between 2
devices independently of other devices being
CHANNEL 15 PAN ID=10
PROPOSED
1
LOCATION
20%
WEBS
CONTROLLER
Fig. 13. Two wireless networks covering a maximum of 5 hops each.
Once the network is deployed and all wireless
thermostats are present and functioning as routers, the
ability of the network to efficiently route wireless signals
cannot be compared to this simple survey analysis
method.
62-2024—03
84%
84%
41%
41%
43%
43%
39%
39%
33%
33%
36%
36%
C
PROPOSED WEBs-AX CONTROLLER WITH WIRELESS COMMUNICATION CARD
Fig. 11. Proposed floor plan with three hop radiuses.
1
20%
20%
Fig. 12. Maximum of 5 hops from controller.
2
20%
20%
20%
3
65%
57%
57%
24%
63%
63%
28%
each thermostat location has been confirmed to
have a signal strength of 10% or greater.
2
20%
present in between. If adding another network,
use a different PAN ID and Channel on the
second network. If additional networks, alternate
between Channel 15 and Channel 25 for each
level.
5
20%
4
CHANNEL 25 PAN ID=20
4
3
20%
20%
5
8
23%
35%
C
58%
20%
20%
3
4
20%
20%
2
1
MCR32619
5
MCR32623
PROPOSED
LOCATION
WEBS
20%
CONTROLLER
MCR32624

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tb7300 seriesTb7600 seriesTbst-5014w