Honeywell Class 320 Meter Installation Instructions Manual page 48

Class 320 advanced kwh/demand meter
Table of Contents

Advertisement

CLASS 320 METER
Address Registers Format
6
3
44001
1 per
4
44007
interval
2 per day Custom Interval Data Headers
5
45501
8
6
46025
8
7
46049
46057
8
46513
8
46521
8
1. To clear single meter kWh/kVARh, set multiple points at 40001 or 41001 for 8 points
with data set to 0000 0000 0000 0000 0000 0000 0000 0000.
2. External inputs are standard on Class 500 meters.
To clear external inputs, set multiple points at 41083 or 41085 for 2 points with data
set to 0000 0000. Jumper J6 must be closed.
3. To set the interval data day block, set multiple points at 44001 for 6 points with data
set to 0C0I 0000 MMDD YYYY 0000 0000.
0C = Channel, 0I = Interval (0F = 15 minute intervals, 05 = 5 minute intervals)
4. Each register represents a 15 or 5 minute kWh pulse value based on the interval
day block. 96 registers max with 15 minute intervals. 288 registers max with 5 minute
intervals. The first interval data register 44007 represents the pulse count for the first
15 or 5 minute interval beginning at midnight.
5. The interval data headers represent days with available interval data. Each day
represents 2 registers. Format: MMDD YYYY.
6. To set the date and time, set multiple points at 46025 for 4 points with data set to
HHMM SSDW MMDD YYYY (DW=day of week)
7. To change the ModBus ID, set single point at 46050 with data set to new ModBus
ID (e.g. 1 to 247). Jumper J6 must be closed.
62-0397-02
ModBus Customer Point Map: CL320
Custom Interval Day Block
Integer Interval Data
Custom RTC Date/Time
Custom EZ7 ID, ModBus ID, Serial Number
Custom Recorder Info., Demand Interval
Custom Flags L1: Power Failure, Battery
Custom Flags L2: Power Failure Date
Description
48
CL
Units
320
R/W
Pulse