Sensor Menu; Menu Tree; Table 11 Menu Tree - Honeywell XYR 6000 User Manual

One wireless series wcx series valve position sensor
Hide thumbs Also See for XYR 6000:
Table of Contents

Advertisement

OneWireless™ Series User Manual
5.5

Sensor Menu

Menu tree

At the PV display, press Enter to access the menus. To interact with the menus use the device local
configuration onscreen buttons (page 31) or the buttons on your PDA.
Table 11. Menu tree
Menu item
CAL
RADIO
PRI RSSI
SEC RSSI
WFN ID
DEV ADD
TX POWER
Description
Calibration menu. Do not use. Device is calibrated at the factory. See section 3.6 for
setting the range or converting the units.
Radio menu
Primary receive signal strength. Read only. Signal strength 00 is too weak to connect to
the network.
Displayed value
Value dBm
00
< -86
01
-86 to -81
02
-80 to -75
03
-74 to -69
04
-68 to -63
05
-62 to -57
06
-56 to -51
07
-50 to -45
08
-44 to -11
09
≥ -10
Secondary receive signal strength. Same as PRI RSSI. Read only.
Wireless Field Network ID. Read only.
Device address. Read only.
Radio transmit power. Read only.
Issue 3
Rx Margin dB
< 10
10 to 15
16 to 21
22 to 27
28 to 33
34 to 39
40 to 45
46 to 51
52 to 85
Saturation
Honeywell Sensing and Control
50040849
5. 4BOperation
5.5. Sensor Menu
27