Communication; Rs232 Port; Relay Interface Card (Option); Snmp Interface Card (Option) - GE 600 - 1500 VA User Manual

600 - 1500 va
Table of Contents

Advertisement

g
4.1
RS232 Port (fig. 8)
The RS 232 Port is a plug-in interface port (9-pin, Sub-D, male) which enables advanced communication
between the UPS and the computer (UPS software required). The interface port is operative as soon as
the mains power cord is plugged into a live wall outlet, even if the UPS is switched off.
We strongly recommend to use only original GE Digital Energy software products in combination with
the interface port.
Pin #
Function
1
RS232 input (UPS shutdown)
2
RS232 output
1)
3
General alarm
4
Plug and Play
5
Common
6
Bypass active
7
Battery low
8
UPS connected
9
Mains failure
1)
Active if the output voltage of the UPS is no longer
guaranteed due to other circumstances than already
indicated by pin 6-7-9:
-
Output converter overload
-
Overtemperature (pre-)alarm
-
High charger voltage
-
Bypass out of limits
Inverter shutdown (due to inverter failure or batt. failure)
-
4.2

Relay Interface Card (option)

The card is equipped with potential free change-over contacts for the following alarms:
mains failure
general alarm
battery low
bypass active
For more information please refer to the user manual that comes with the interface card.
4.3

SNMP Interface Card (option)

This card allows the data interface to be connected directly to an Ethernet network.
For more information please refer to the user manual that comes with the interface card.
OPM_NPE_19X_600_1K5_2GB_V030

4 - Communication

fig. 8
9
GE DE NetPro 19" 600-1500: User manual 3.0 (GB)
GE Digital Energy
5 = COMMON
8 = UPS CONNECTED
MAINS FAILURE
DC
PnP
RS232
GENERAL ALARM
BATTERY LOW
BYPASS ACTIVE
DC
DATA FROM
UPS
RS232
DATA TO UPS
DC
RS232
REMOTE UPS
SHUT DOWN
MAX: +48V 100mA
5
9
4
8
3
7
2
6
1
RS232
PORT

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Digital energy netpro 19”

Table of Contents