Operating Manual
Uninterruptible Power supply
Digital Energy™
LP 33 Series
10 – 20 – 30 kVA
400 Vac CE / Series 4
GE Consumer & Industrial SA
General Electric Company
CH – 6595 Riazzino (Locarno)
Switzerland
T +41 (0)91 / 850 51 51
F +41 (0)91 / 850 51 44
www.gedigitalenergy.com
GE imagination at work

Advertisement

Table of Contents
loading

Summary of Contents for GE LP 33 Series

  • Page 1 Uninterruptible Power supply Digital Energy™ LP 33 Series 10 – 20 – 30 kVA 400 Vac CE / Series 4 GE Consumer & Industrial SA General Electric Company CH – 6595 Riazzino (Locarno) Switzerland T +41 (0)91 / 850 51 51 F +41 (0)91 / 850 51 44 www.gedigitalenergy.com...
  • Page 2 The present publication and any other documentation supplied with the UPS system is not to be reproduced, either in part or in its entirety, without the prior written consent of GE. The illustrations and plans describing the equipment are intended as general reference only and are not necessarily complete in every detail.
  • Page 3 We thank you for selecting our products and are pleased to count you amongst our very valued customers at GE. We trust that the use of the LP 33 Series Uninterruptible Power Supply system, developed and produced to the highest standards of quality, will give you complete satisfaction.
  • Page 4: Table Of Contents

    RPA system - Control bus connection............................34 UPS FUNCTIONING AS FREQUENCY CONVERTER ......................36 LAYOUT................................. 37 LAYOUT LP 33 Series / 10 - 20 kVA ............................37 LAYOUT LP 33 Series / 30 kVA ..............................38 SYSTEM HANDLING............................. 39 CONTROL PANEL..................................... 39 COMMAND PUSH BUTTONS AND SWITCHES........................
  • Page 5 Restore to normal operation after “EPO – Emergency Power Off”................62 PROCEDURES FOR PARALLEL SYSTEM LP 33 Series......................63 8.2.1 Parallel System start-up of the LP 33 Series..........................63 8.2.2 Parallel UPS shutdown with load transfer on manual bypass (Q2)................65 8.2.3...
  • Page 6: Safety Rules

    UPS system. NOTE ! LP 33 Series / 10 - 20 - 30 kVA is a Class A-UPS Product (according to EN 50091-2). In a domestic environment, this product may cause radio interference, in which case, the user may be required to take additional measures.
  • Page 7: Important Safety Rules

    It is important that air can move freely around and through the unit. • Do not block the air vents. • Avoid locations in direct sunlight or near heat sources. Modifications reserved Page 7/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 8 Observe carefully the safety instructions to prevent risk of electrical shock. Parallel version secured with RPA When included in the text, this symbol refers to operation needed only for parallel system Modifications reserved Page 8/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 9 9 Where conductors may be exposed to physical damage, protect the conductors in accordance with all applicable codes. 10 If you are replacing the battery or repairing battery connections, shut OFF the UPS and remove the battery fuses. Modifications reserved Page 9/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 10: Safety Symbols And Warnings

    Used when moving the equipment due to the heavy weight. DANGER OF OVERHUNG LOAD Used when the equipment is lifted by a crane. DO NOT TOUCH Risk of parts with hazardous voltages or parts in movement. Modifications reserved Page 10/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 11: Introduction

    INTRODUCTION GENERAL DESCRIPTION The LP 33 Series Uninterruptible Power Supply (UPS) provides the energy supply for critical loads which need a reliable, continuous free from voltage disturbances and frequency fluctuations supply. In case the mains fails, or it exceeds the permitted tolerances, the energy to supply the load is furnished by the battery with a backup time dependent on its capacity, until the mains recovers.
  • Page 12: Description

    If chosen the ECO Mode, the SSM transfer the load from mains to inverter in case the utility fails. Back-Feed Protection All LP 33 Series UPS’s are equipped with an automatic system for the protection against voltage back feeding towards Utility, through the Bypass (Applied Standard IEC 62040-1).
  • Page 13: Operation Modes

    ECO Mode cannot be enabled for RPA Parallel System. Attention: A single unit equipped with a RPA - Parallel board, must be considered as parallel, thus disabling ECO Mode. Modifications reserved Page 13/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 14 When enough inverters to supply the load have been restarted, the load will be transferred from the automatic bypass back to the inverter bus-bars. Modifications reserved Page 14/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 15 As the warning occurs on one unit necessary to support the present load, the system starts the timeout (selectable) of “stop operation” and then the output load shuts down. Modifications reserved Page 15/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 16: Rpa Parallel System

    RPA PARALLEL SYSTEM The RPA (Redundant Parallel Architecture) allows to extend the unit to a parallel system with 2, 3, or 4 units LP 33 Series connected on the same bus, which ensure the highest reliability rate and increase the power availability.
  • Page 17: Service And Technical Support

    Fig. 3.4-1 Identification label WARRANTY GE, operating through its authorised agents, warrants that the standard products will be free of defects in materials and workmanship for a period of 24 months (12 months for battery), after the date of the invoice, or such other period as may be specified.
  • Page 18: Recycling At The End Of Service Life

    WARNING ! Leads contained in the batteries is a dangerous substance for the environment, therefore it must be correctly recycled by specialised companies! Modifications reserved Page 18/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 19: Installation

    UPS. WARNING ! When loading / downloading and when moving the UPS, it is forbidden: When loading / downloading and when moving the UPS, pay attention to: Modifications reserved Page 19/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 20: Dimensions And Weights

    Fig. 4.1.1-2 Dimensions with carton package 31.5” x 35.9” x 63.0” 508 lbs 1’301 (21Ah) NOTE ! The weight of each single piece is marked outside the package! Modifications reserved Page 20/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 21: Delivery

    Service Centre before putting the UPS into operation. NOTE ! In case of storage of the UPS pay attention to: SENSITIVE SENSITIVE SENSITIVE FRAGILE TO DAMPNESS TO HEAT TO FROST Modifications reserved Page 21/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 22: Storage Of The Battery

    2 months with storage temperature 35°C (95°F) NOTE ! In case of battery storage pay attention to: SENSITIVE SENSITIVE SENSITIVE FRAGILE TO DAMPNESS TO HEAT TO FROST Modifications reserved Page 22/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 23: Place Of Installation

    Respect the prescription VDE 0510, those of the battery supplier and other local standards. The installation and cabling of the battery must be done by qualified people. Modifications reserved Page 23/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 24: Ventilation And Cooling

    UPS. Do not put any object on the top of the cabinet: it might obstruct the air flow. Fig. 4.5-1 Airflow through the LP 33 Series Heat evacuation from UPS room The heat must be evacuated from the environment with a proper cooling / ventilation system provided by the user.
  • Page 25: Unpacking

    This has to done with the utmost care! NOTE ! Be aware of the heavy weight of the UPS, in particular if already equipped with Batteries. LP 33 Series unpacking sequence Fig. 4.6-1 Modifications reserved Page 25/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 26 The UPS can also be screwed directly to the floor on each leg. Fig. 4.6-2 Bolts to block the LP 33 Series on it’s position NOTE ! The wheels are designed only for limited movements on the installation site.
  • Page 27: Electrical Wiring

    UPS can be moved for maintenance purpose. It is recommended to use flexible input/output conductors with suitable length to admit a sufficient displacement. Modifications reserved Page 27/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 28: Fuse Discrimination (Co-Ordination Of Breakers Tripping)

    If the selectivity must be ensured also in case of mains failure (that means inhibit automatic bypass), the largest fuse in the output distribution must be lower than 20% of the UPS rated current for each phase. Modifications reserved Page 28/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 29: Fuse Ratings

    3 x 35 A 2 x 50 A LP 33 Series / 30 kVA 3 x 63 A 3 x 63 A 3 x 50 A 2 x 80 A Modifications reserved Page 29/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 30: Input / Output Cable Ratings

    4 x 2.5 (4 x 4) 5 x 2.5 (5 x 4) 4 x 2.5 (4 x 4) LP 33 Series / 20 kVA 5 x 10 (5 x 16) 5 x 10 (5 x 16) 4 x 6 (4 x 10)
  • Page 31: Electrical Connection

    Input/output terminals must be tightened with proper screwdriver applying torsion force 1,2 / 1,4 Nm. Fig. 4.8.1-3 Common input mains connection Clamp the input/output cables with the included cable-ties “A”. Modifications reserved Page 31/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 32: Power Connection With Separate Input Mains (Option)

    L3 = Phase L2 load N2 = Neutral load PE = Earth load NOTE ! For UPS correct operation, the input mains phase rotation must be clock-wise. Modifications reserved Page 32/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 33: External Battery Connection

    F10 (0) = Central point of battery blocks F11 (-) = Negative pole Fig. 4.8.3-1 External battery connection to UPS NOTE ! Clamp the input/output cables with the included cable-ties “A”. Modifications reserved Page 33/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 34: Rpa System - Control Bus Connection

    Do not insert or remove J3 and J4 from the board “P16 - Connector adapter RPA” when the parallel system is operating. Fig. 4.8.4-3 Connection to Board P16 Modifications reserved Page 34/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 35 The standard length of the control bus cable between two parallel unit is 8 m / 26 ft. NOTE ! Connection and commissioning of an additional UPS to an existing parallel system, Service Centre. must be performed by a service engineer from of your Modifications reserved Page 35/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 36: Ups Functioning As Frequency Converter

    UPS FUNCTIONING AS FREQUENCY CONVERTER When the UPS LP 33 Series is delivered as frequency converter (different output frequency with respect to the input frequency), the automatic bypass and manual bypass functions are disabled. Therefore the load cannot be transferred to mains in case of overload, short circuit, or inverter failure.
  • Page 37: Layout

    LAYOUT LAYOUT LP 33 Series / 10 - 20 KVA Fig. 5.1-1 General view Fig. 5.1-2 Front view Fig. 5.1-3 Side view Fig. 5.1-4 Control panel RPA board (option) SNMP Card (option) Customer Interface (option) Relay Card Serial port RS232...
  • Page 38: Layout Lp 33 Series / 30 Kva

    Output switch Q1 Fuses F1-F2-F3 (Rectifier Input) Identification data label Fuses F9 - F10 - F11 (Battery) Fig. 5.2-5 Front view without panels Fig. 5.2-6 Power connection view Modifications reserved Page 38/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 39: System Handling

    It remains lit also when the output switch Q1 is open or battery disconnected. LED Operation When lit, it means the UPS is correctly operating and the load is powered by the (green) inverter. When blinking, it means SERVICE REQUIRED Modifications reserved Page 39/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 40: Command Push Buttons And Switches

    Mains failure of long duration or low Battery voltage will cause the automatic shutdown of the UPS, thus preventing damage to the Battery. Fig. 6.2-4 Battery fuses Modifications reserved Page 40/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 41: Lcd Screen

    Access to the Parameters for setting the SBM mode is password protected. Please call your Service Centre. Battery charge level. Estimated battery backup time with actual load. Modifications reserved Page 41/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 42 ECO Mode operation. NR FAST TRANSIENT <2ms >2ms >5ms >10ms The number of fast transients occurred on the bypass utility on the last seven days. Modifications reserved Page 42/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 43: Event Screens (Alarm)

    “stop operation” time to the actual load. Dangerous high UDC-Voltage. HIGH BATTERY Causes Inverter shutdown. inverter restarts automatically 4116 VOLTAGE after return to normal floating voltage. Modifications reserved Page 43/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 44 The mains bypass voltage is out of the tolerances (±10%). BYPASS MAINS K6 opens, synchronisation with mains is inhibited and 4410 OUT OF TOLERANCE transfer to mains is blocked. Modifications reserved Page 44/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 45 (time depending on the % of overload). Load Off after time-out of “stop operation” with missing LOAD OFF DUE TO mains due to battery low voltage or overtemperature 4999 UBATT OR TEMP. condition. Modifications reserved Page 45/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 46: Messages List

    Inverter cannot be switched OFF, because the load cannot be 4303 CANNOT BE transferred on mains (voltage out of tolerance, not TURNED OFF synchronising, bypass blocked). Code Message Meaning Modifications reserved Page 46/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 47 The function ECO Mode is enabled, and according to the time COMMAND UPS program the UPS will run in ECO Mode, supplying the load 4601 STAND BY normally by mains. Code Message Meaning Modifications reserved Page 47/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 48 Commands source can be chosen depending on the value of respective parameter (password required): REMOTE CONTROL 4764 0 = Only local panel 1 = Only serial port on CI (TLC) 2 = Both Modifications reserved Page 48/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 49: Event Report Lp 33 Series

    Description of repair action taken: Event No. Code Status Date Hour ......……………………………..…………………......………..........……………………………..…………………......………..........……………………………..…………………......………..........……………………………..…………………......………..........……………………………..…………………......………....Actual situation: ......……………………………..…………………......………..........……………………………..…………………......………..........……………………………..…………………......………..........……………………………..…………………......………..........……………………………..…………………......………....Remarks: ......……………………………..…………………......………..........……………………………..…………………......………..........……………………………..…………………......………..........……………………………..…………………......………..........……………………………..…………………......………....Modifications reserved Page 49/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 50: Menu Screens (Menu)

    APPLIC. ON UTILITY if the output is powered by mains or APPLIC. PROTECTED when the load is normally powered by the inverter. Modifications reserved Page 50/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 51: User Parameters Screen

    It is useful because since the events typically do not occur isolated but in certain sequences, you can eliminate the need for multiple dial-outs for such a sequence of events. Modifications reserved Page 51/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 52 In case this minimum time in VFI Mode is not respected, the ECO Mode will be disabled. If the value is N, the UPS is normally operating in VFI / double conversion mode at all times. Modifications reserved Page 52/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 53 - Monday - Tuesday - Wednesday - Thursday - Friday ECO START 00:00 00:00 18:00 18:00 18:00 18:00 18:00 ECO STOP 23:59 23:59 06:00 06:00 06:00 06:00 06:00 Modifications reserved Page 53/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 54 • ECO Mode screen how many hours of ECO Mode operation have been selected for each day of the week. NOTE ! The ECO Mode becomes active only if the load is supplied from inverter. Modifications reserved Page 54/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 55: Operation

    Insert the battery fuses F9, F10, F11 and eventual external fuses in case of external battery. ► Continue Modifications reserved Page 55/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 56 = 70% Operation mode selection. LP 33 Series is delivered normally selected for permanent VFI operation. ECO Mode can be enabled and the ECO Mode START time & ECO Mode STOP time can be programmed for each day of the week (see Section 7.3.1-5).
  • Page 57: Ups Shutdown With Load Transfer On Manual Bypass (Q2)

    Perform the command total off. Remove the rectifier-input fuses F1, F2, F3 and the battery fuses F9, F10, F11 (remove the external battery fuses in case of external battery). ► Continue Modifications reserved Page 57/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 58 The UPS cabinet contains parts electrically live. Apart from the front door, do not open any other part of the UPS. NOTE ! With separate mains inputs, it’s possible to disconnect mains rectifier. Modifications reserved Page 58/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 59: Start-Up Following The Operation On Manual Bypass (Q2)

    Some seconds later the load will be transferred on inverter and LP 33 20kVA the main screen will display: APPLICATION ON UPS APPLICATION ON UPS = 70% END OF PROCEDURE Modifications reserved Page 59/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 60: Complete Shutdown

    15 minutes. Wait until capacitors are completely discharged before starting the UPS again. Apart from the front door, do not open any other part of the UPS. Modifications reserved Page 60/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 61: Restore To Normal Operation After "Total Off

    MENU/COMMAND MENU/INVERTER ON INVERTER ON INVERTER OFF LP 33 20kVA APPLICATION ON UPS The LCD screen must display the status: APPLICATION ON UPS = 70% END OF PROCEDURE Modifications reserved Page 61/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 62: Restore To Normal Operation After "Epo - Emergency Power Off

    The load will be automatically transferred from mains to the inverter. LP 33 20kVA APPLICATION ON UPS The LCD screen must display the status: APPLICATION ON UPS = 70% END OF PROCEDURE Modifications reserved Page 62/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 63: Procedures For Parallel System Lp 33 Series

    PROCEDURES FOR PARALLEL SYSTEM LP 33 Series 8.2.1 Parallel System start-up of the LP 33 Series Before connecting hazardous voltages, make sure that: • The connection to the electrical system has been performed by qualified personnel; • The equipment frame has been correctly grounded to the main earth;...
  • Page 64 It is recommended to recharge the battery during a few hours in order to provide the complete battery energy stored to the load in the event of mains failure. Modifications reserved Page 64/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 65: Parallel Ups Shutdown With Load Transfer On Manual Bypass (Q2)

    Remove the rectifier-input fuses F1, F2, F3 and the battery fuses F9, F10, F11 (remove the external battery fuses in case of external battery) on each unit. ► Continue Modifications reserved Page 65/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 66 The UPS cabinet contains parts electrically live. Apart from the front door, do not open any other part of the UPS. NOTE ! With separate mains inputs, it’s possible to disconnect mains rectifier. Modifications reserved Page 66/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 67: Start-Up Following The Operation On Maintenance Bypass (Q2)

    APPLICATION ON UPS is achieved on inverter side. = 70% The main screen of each unit will display: APPLICATION ON UPS END OF PROCEDURE Modifications reserved Page 67/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 68: Shutdown Of A Single Unit In A Parallel System

    If an intermediate unit must be disconnected from a parallel system pay attention do not open the control bus: keep the plugs J3 and J4 connected to the board “P16 - Connector adapter RPA” (see Section 4.8.4). Modifications reserved Page 68/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 69: Start-Up An Additional Unit In A Parallel System

    APPLICATION ON UPS will be shared with the other units. = 70% The main screen of each unit will display: APPLICATION ON UPS END OF PROCEDURE Modifications reserved Page 69/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 70: Complete Shutdown Of A Parallel System

    15 minutes. Wait until capacitors are completely discharged before starting the UPS again. Apart from the front door, do not open any other part of the UPS. Modifications reserved Page 70/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 71: Restore To Normal Operation After "Total Off

    APPLICATION ON UPS will transfer to inverter. = 70% The LCD screen must display on all Units the status: APPLICATION ON UPS END OF PROCEDURE Modifications reserved Page 71/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 72: Restore To Normal Operation After "Epo - Emergency Power Off

    APPLICATION ON UPS will transfer to inverter. = 70% The LCD screen must display on all Units the status: APPLICATION ON UPS END OF PROCEDURE Modifications reserved Page 72/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 73: Customer Interface

    (Slot 1 - J4) J27 - RS232 Fig. 9-1 Slot connectivity LP 33 Series is supplied by a standard Serial Port J27 - RS232 (see Section 9.1) and a Relay Card (see Section 9.2). List of possible connectivity configurations on LP 33 Series Slot 1 –...
  • Page 74: Serial Port J27 - Rs232

    The serial port J27 - RS232 is enabled on all the units of the parallel system. Serial port J27 – RS232 connection to PC with RS232 1:1 cable DB9m – DB9f Fig. 9.1-2 Serial port J27 - RS232 connection to PC Modifications reserved Page 74/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 75: Relay Card

    The function GEN-ON is not available on the Relay Card. In case this function is needed, the optional Customer Interface card must be installed (see Section 10.2.1). Modifications reserved Page 75/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 76: Epo (Emergency Power Off)

    Perform the command INVERTER OFF entering the screen: COMMAND MENU MENU/COMMAND MENU/INVERTER OFF. INVERTER ON INVERTER OFF • Start the inverter entering the screen: COMMAND MENU MENU/COMMAND MENU/INVERTER ON. INVERTER ON INVERTER OFF Modifications reserved Page 76/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 77: 10 Options

    UPS in order to guarantee safe and orderly shutdown of the server, when needed. Connectivity Software JUMP Software Suite / IRIS Service, etc. Software application for the control and monitoring of the UPS. Modifications reserved Page 77/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 78: Options Assembly And Connection

    P2 – Mainboard are OFF (see Fig. 10.2.1-3). NC = Normally Closed Programmable functions on input contacts X1/10, 21 or J2/10, 23 Programmable X1/11, 22 or J2/11, 24 Programmable / Generator ON (NO) Modifications reserved Page 78/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 79 Consult your nearest Service Centre for more information. In a parallel system a separate NO (Normally Open) contact must be connected to each individual unit. Modifications reserved Page 79/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 80 Perform the command INVERTER OFF entering the screen: COMMAND MENU MENU/COMMAND MENU/INVERTER OFF. INVERTER ON INVERTER OFF • Start the inverter entering the screen: COMMAND MENU MENU/COMMAND MENU/INVERTER ON. INVERTER ON INVERTER OFF Modifications reserved Page 80/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 81: Optional Battery Cabinet Connection

    F9, F10 and F11 at the front of the UPS must not be inserted until the start-up operation of the UPS. Fig. 10.2.2-4 PCB P2 - Mainboard Modifications reserved Page 81/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 82: 11 Maintenance

    The service life of the battery is from 3 to 6 years, depending on the operating temperature and on the number of discharge cycles. The UPS LP 33 Series offers the possibility of SBM (Superior Battery Management). The function SBM can be activated through a service Parameter.
  • Page 83: Service Required

    We highly recommend that you contact your Service Centre for preventive maintenance work. NOTE ! Ask to your local Service Centre to submit the form of Preventive Maintenance Contract suitable for your specific needs. Modifications reserved Page 83/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 84: 12 Notes

    It is recommended to note in this section Notes, with date and short description all the operations performed on the UPS, as: maintenance, components replacement, abnormal situations, etc. . Date Description Done by Modifications reserved Page 84/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...
  • Page 85: 13 Annex

    Can be found in the final section and are listings of the technical data of the UPS. 13.2 SCHEMATICS These are included in the last section and include the UPS functional drawings. Modifications reserved Page 85/85 OPM_LPS_33E_10K_30K_4GB_V030.doc Operating Manual LP 33 Series / 10-20-30 kVA...