Panasonic EBL128 Planning Instructions page 72

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
14
One or more interlocking inputs, in the specified
interlocking area, are activated.
15
The interlocking input, in the specified interlocking
area/point, is activated.
16
One or more interlocking inputs are activated.
17
One or more interlocking inputs, in the specified range,
are activated (from interlocking area no./point to
interlocking area no./point).
18
Output activated when input trigger condition "Activated
routing equipment" is true.
the alarm has been reset.
19
Routing equipment output "Fault tx" is activated or input
trigger condition "Activated fault routing equipment" is
71
true.
20
Routing equipment output (Fire brigade tx) is disabled.
21
The specified zone is disabled.
22
The specified alarm point (zone/address) is disabled.
23
One or more alarm points (zone/address) are disabled.
24
One or more faults are generated in the system.
25
Loss of mains (in a c.i.e.). NOTE! The output(s) will be
activated immediately but the corresponding fault is
normally delayed.
26
This control expression is true for 5 seconds, whenever a
reset pulse is sent to the specified zone/address.
27
The programmed time channel (1-12) is activated.
28
Alert annunciation activated (by any alarm point set to
activate this function).
or becomes a normal fire alarm.
see EBL128 Operating Instructions.
29
Alert annunciation activated (by any alarm point set to
activate this function) and acknowledged.
AA alarm is reset or becomes a normal fire alarm.
more information, see EBL128 Operating Instructions.
30
Door open in EBL128 / ext. FBP.
31
Key cabinet alarm. For more information, see EBL128
Operating Instructions.
32
General control disabled (via menu H2/B7).
33
General alarm device disabled (via menu H2/B8
"Silence alarm devices).
70
Indicated by LED "Fire brigade tx". Output can be tested via menu H1.
71
Indicated by LED "Fault tx activated". Output can be tested via menu H1.
72
Indicated by LED "Fault/Disablements Fire brigade tx".
73
Indicated by LED "Disablements".
74
Indicated by LED "General fault" and/or LED "Fault tx activated".
75
Or ext FBPs connected to the control unit.
Indicated by LED "Door open".
EBL128 Planning Instructions V1.1.x
70
The output is activated until
Valid until the AA alarm is reset
For more information,
75
70
72
73
74
Valid until the
For
73
76
or via