Control Unit Output R0; Relay Outputs Expansion Board 4581 Output 0 - Output 7; Inputs And Outputs Expansion Board 4583 Output 0 - 1 - Panasonic EBL128 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
9.2
9.3
9.4
S0
Supervised (monitored) voltage output, 24V DC
mA (Fuse F8).
S1
Supervised (monitored) voltage output, 24V DC
mA (Fuse F6).
As default S0-S1 are set to type "Alarm device", "Intermittent 0.8 /
0.8, normally low, supervised and trigger condition "General fire".
Connections and more information, see drawing 128-22.
See also chapter "Programmable voltage outputs (S0-S1)", page 18.

Control unit output R0

EBL128 has one programmable relay output:
R0
Relay output, NO or NC contacts
As default R0 is set to type "Routing equipment" (Fire brigade tx),
Steady (cont.), normally open and trigger condition "Fire brigade tx".
Connections and more information, see drawing 128-23.
8 relay outputs expansion board 4581
Output 0 – Output 7
Each 4581 board has eight programmable relay outputs:
Output 0
Relay output, NO or NC contacts programmable
Output 1
Relay output, NO or NC contacts programmable
Output 2
Relay output, NO or NC contacts programmable
Output 3
Relay output, NO or NC contacts programmable
Output 4
Relay output, NO or NC contacts programmable
Output 5
Relay output, NO or NC contacts programmable
Output 6
Relay output, NO or NC contacts programmable
Output 7
Relay output, NO or NC contacts programmable
Relay contact ratings: Max. 2A @ 30 V DC.
Connections and more information, see dwg. 128-30.
Inputs and Outputs expansion board 4583
Output 0 – 1
Expansion
board
4583
59
(monitored)
voltage outputs:
Output 0
Supervised (monitored) voltage output, 24V DC
200 mA (Fuse F1).
Output 1
Supervised (monitored) voltage output, 24V DC
200 mA (Fuse F2).
Connections and more information, see drawing 128-33.
See also chapter "Inputs and outputs expansion board 4583", page 26.
for a value outside this range. A normally high output will be low for a few
seconds during restart of EBL128.
60
See chapter "Technical data", page 143, regarding system voltage.
61
Relay contacts: max. 1 A @ 30 V DC.
EBL128 Planning Instructions V1.1.x
61
programmable.
has
two
programmable,
62
60
, max. 500
60
, max. 200
supervised
60
, max.