Panasonic EBL128 Planning Instructions page 36

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
Zone-Addr.
001-01 (smoke)
001-02 (heat)
Techn. addr.
123
Zone-Addr.
001-01 (smoke
or heat)
Techn. addr.
123
Terminals for ext. LED 2217 /2218. Recess for label holder
3391. The technical address is set with an Address setting tool
(AST) 3314. The Address setting tool 3314 is also used for
mode setting:
NORMAL mode: 3309 is in this mode via Win128 set to one
of three algorithms (static response temp. range) for class:
A1 (54-65°C), min./typical/max. ambient temp. -20/+25/+50°C
A2 S (54-70°C), min./typical/max. ambient temp. -20/+25/+50°C
B S (69-85°C), min./typical/max. ambient temp. -20/+40/+65°C
2330 mode: Not used in EBL128.
2312 mode: Not used in EBL128.
4300 Analog multi detector. A smoke detector and a heat detector
within one housing. Scattered light (i.e. reflection of infrared
light) is used to detect smoke and the heat sensing element is a
thermistor.
The detector has unleaded soldering.
To be plugged in an ASB base 3312. Built-in LEDs are lit to
indicate that the detector
for mechanical lock (screw attached).
Via Win128 it is programmable how the detectors shall operate:
a)
Two presentation numbers (addresses): The detector
unit works as two separate detectors. The smoke detector is
programmed for one zone-address and the heat detector for
another zone-address
detectors during working hours and in control expressions for
programmable outputs). The detector unit has one technical
address used for programming and fault presentation.
b)
One presentation number (address): The detector unit
works as one detector and is programmed for one zone-address.
The detector unit (actually the heat detector) can detect a
methylated spirits fire (EN54-9, test fire TF6; liquid fire), which
normally is impossible for a photo electric smoke detector to
detect. The detector unit has one technical address used for
programming and fault presentation.
It is, via Win128, programmable if the detectors in alt. b) shall
work with "OR-functionality" or with a "Decision algorithm":
b1)
OR-functionality: Either the heat detector or the
smoke detector will activate fire alarm. This alternative is
recommended in most cases. The detector unit has one
technical address used for programming and fault
presentation.
35
I.e. the heat detector and/or the smoke detektor.
36
The zone number has to be the same for both detectors. NOTE! When
counting alarm points these "two detectors" are regarded as two alarm points.
EBL128 Planning Instructions V1.1.x
35
has generated fire alarm. Prepared
36
. (Can be used to disable one of the