Specifications - Honeywell TB7200 Series Application Manual

Pir application guide
Table of Contents

Advertisement

PIR Status LED's
The PIR covers have 2 green status LEDs behind the PIR lens that can be used for diagnostic purposes during commissioning or
servicing. (Fig. 8)
These LEDs are used to indicate a local movement detected by the PIR cover.
— The status LEDs start to function to indicate movement 1 minute after the initial power up of the thermostat.
— The status LEDs will only remain active to indicate sensed movement 30 minutes after the initial power up of the
thermostat.

SPECIFICATIONS

PIR cover power requirements: 5 Vdc max current draw of 7mA
Operating conditions: 0 C to 50 C (32 F to 122 F); 0% to 95% R.H. non-condensing
Storage conditions: -30 C to 50 C (-22 F to 122 F); 0% to 95% R.H. non-condensing
Sensor: Local Passive Infrared Sensor
Dimensions: 4.94 in. x 3.38 in. x 1.0 in.
Approximate shipping weight: 0.1 lb
Agency Approvals:
UL: UL 873 (US) and CSA C22.2 No. 24 (Canada), File E27734 with CCN XAPX (US) and XAPX7 (Canada)
FCC: Compliant to CFR 47, Part 15, Subpart B, Class A (US)
Industry Canada: ICES-003 (Canada)
CE: EMC Directive 89/336/EEC (Europe Union)
PIR APPLICATION GUIDE FOR TB7200 AND TB7300 SERIES THERMOSTATS
Fig. 8. LED status lights.
35
63-4526—01