11. TB7300 stand-alone fan coil application—3 levels of occupancy with dual PIR sensors
Set-up and Configuration
Thermostat used
PIR used
BI2 Configuration
Stand-by timer value
Unoccupied timer value
Network interface used
Sequence of operation:
Occupied
Stand-By
Unoccupîed
Initial State at
Power-Up = Stand-By
At initial power-up, when the thermostat 24 Vac power supply is applied; the initial occupancy of the zone will be stand-by mode if
the PIR devices do not detect any movement.
As soon as a PIR device detects a movement or motion, the occupancy status switches to occupied and the occupied setpoints
are used. The room will then be in occupied mode until a door toggle is detected.
If a door toggle is detected, then the room switches to stand-by mode and the stand-by setpoints are used. If any occupants are
left in the room, local movements must be seen to resume the occupied mode.
While in stand-by mode, if no motion is detected in the zone for the entire unoccupied timer duration, then the room switches to
unoccupied mode and the unoccupied setpoints are used.
At anytime, if the PIR device detects a local movement or motion, the occupancy status switches to occupied and the occupied
setpoints are used.
PIR APPLICATION GUIDE FOR TB7200 AND TB7300 SERIES THERMOSTATS
TB73x5X5014X (lodging models)
BI1 configured for remote PIR sensor
and TB-PIR-FCU-L cover
Door dry contact
2.0 hours
6.0 hours
None, stand-alone
Always
Occupied
Door Open/Close
Toggle Detected
Door Switch
Door Switch
Unoccupied Time
= 6 Hours
Time
31
Remote PIR Sensor
Remote PIR Sensor
Unoccupied Time Elapsed
= Unoccupied Mode
63-4526—01