Troubleshooting; System Status And Error Codes - Honeywell AQ251 User Operation And Maintenance

Aquatrol aq251 series zone synchronizing boiler reset controls
Hide thumbs Also See for AQ251:
Table of Contents

Advertisement

AQUATROL ZONE SYNCHRONIZING BOILER RESET CONTROLS

TROUBLESHOOTING

Power Disruption
The AQ251's system and thermostat (zone settings)
parameters are stored in non-volatile memory and are
updated as they change.
When a power disruption or loss of power occurs, the system
configuration is retained in memory.
When power is restored, the AQ251 Control Panel enters
auto-detection mode, reads its previously-stored settings, and
initializes all AQUATROL network components according to
their saved parameters.
POWER DISRUPTION GREATER THAN 4 HOURS
If a power disruption lasts for more than 4 hours, the AQ251
will have discharged its internal super capacitor, and the
DATE and TIME OF DAY settings will need to be reset.
LCD Display
A/C MIN. OFF TIME
A/C MIN. ON TIME
AUX IN EM. SHUT
BOILER:
EM SHUT
FRZ PROT
HEAT DHW
HEATING
IDLE
INIT
INST PURG
NSTALL
PMP EXER
POST PURG Boiler is active with Post Purge operation and is sending the purged water to the Boiler
PURGE DHW Boiler is active with Post Purge operation and is sending the purged water to the DHW
CALL FOR COOL
CALL FOR DHW
CALL FOR HEAT
CWSD ACTIVE
DHW DISABLE
LOST ZONE A-1
...
LOST ZONE D-16
NO DHW PROBE
NO OUTDOOR PROBE
69-1979—04
Table 2. LCD Status Notices and Error Messages.
Parameter
n/a
The A/C compressor is disabled, because the minimum OFF time has not yet elapsed.
n/a
The A/C compressor is active and the minimum ON time has not yet elapsed.
n/a
Auxiliary Input's Emergency Shut Down is active.
Boiler is disabled, because the AQ251 is in Emergency Shut Down mode.
Boiler freeze protection activated:
• Communication between Control Module and Zoning Module has been lost for more
than 1 minute
or
• Boiler supply temperature is less than 50°F (10°C)
Boiler is active to serve DHW.
Boiler is active to serve zones.
Boiler is not active.
Boiler contacts (terminals 22 and 23) on the AQ1520, which are connected to the
boiler's T-T terminals, have been shorted and the boiler is beginning its firing sequence.
Boiler is active while the AQ251 is conducting the PURGE operation in the Installer
Setup.
Boiler is in ready mode during Installer Setup.
Boiler is disabled while the AQ251 is exercising all pumps and valves connected to the
AQUATROL network.
(Primary) loop.
tank.
n/a
At least one zone with a programmable thermostat requires cooling.
n/a
The DHW requires heat.
n/a
At least one zone requires heat.
n/a
Zone calls for cooling are not served because CWSD (Cold Weather Shutdown) is in
progress.
n/a
DHW call is not served because it is disabled.
n/a
Lost communication with a zone (A-1 to A-16, B-1 to B-16, C-1 to C-16, or D-1 to D-16).
n/a
No DHW sensor connected or it is defective.
n/a
No outdoor sensor connected or it is defective.
Upon restart, the AQ251 displays its clock settings as: YEAR
= 2008, MONTH = JAN, DATE = 1. The message PLS SET
DAY/TIME displays. This displayed message continues until
the DATE and TIME OF DAY are updated.
NOTE: If the power failure parameter is set to Backlight
(USER MENU > PREFERENCES/TIME), the LCD
backlight flashes repeatedly, along with the mes-
sage.
The AQ251 remains permanently in OCCUPIED (or Comfort)
mode until the DAY and TIME OF DAY are updated.

System Status and Error Codes

System status alerts and error messages display on the
System Status Page. These messages are shown in Table 2.
Meaning
6