Smoke Dampers; Fire Dampers - Honeywell AUTOMATIC CONTROL SI Edition Engineering Manual

For commercial buildings
Table of Contents

Advertisement

DAMPER SELECTION AND SIZING
In a low leakage damper, materials for the seals are selected
based on the temperature of the air being controlled. Standard
seals can be upgraded to withstand higher temperatures by using
a more heat resistant material. An example would be changing
a blade edge seal from neoprene to silicone rubber.
When duct static pressure is relatively low but leakage must
be minimal, a low leakage damper with reduced static pressure
ratings may be used. Generally, as the strength of a given damper
increases, velocity and static pressure drop capabilities increase.

SMOKE DAMPERS

Any damper that controls airflow is capable of controlling
smoke. In order to apply dampers to smoke control systems
properly, UL 555S, Standard for Leakage Rated Dampers for
Use in Smoke Control Systems, provides classification based
on leakage, differential pressure across the damper, maximum
velocity when the damper is fully open, temperature, and
damper size. This classification includes the specific actuator
used. See Table 1 for leakage classifications.
Table 1. UL 555S Maximum Allowable
Damper Leakage Classifications.
Leakage
Cfm per sq ft at 1
Classification
in. wc
O
I
II
10
III
40
IV
60
3
Approximate
m
/s per sq m
SI Equivalent
at 0.249 kPa
O
I
II
III
IV
In designing a smoke damper, a manufacturer develops a
product line with Maximum A and B and Minimum A and B
dimensions where:
A = Overall damper size in the direction of the blade
length.
B = Overall damper size perpendicular to the blade length.
The three damper sizes tested by UL are Maximum A/Minimum
B, Minimum A/Maximum B, and Maximum A/Maximum B.
Damper testing includes meeting material construction
requirements, cycling, temperature degradation, dust loading,
salt-spray exposure, leakage, and operation at maximum
pressure and velocity.
In testing for temperature degradation, the damper is heated
in the closed position for 30 minutes and then cycled to see that
it operates as intended. Temperature classifications include
121.1 C, 176.7 C, 232.2 C, etc., in increments of 55.6 kelvins.
Cfm per sq ft
at 4 in. wc
0
0
4
8
20
80
120
3
m
/s per sq m
at 0.995 kPa
0
0
0.020
0.041
0.051
0.102
0.203
0.406
0.305
0.610
Generally, Classes I, II, III, and IV are considered appropriate
for smoke control. The class specified should be based on the
application requirements. For example, Classes I and II are
appropriate for mixed air dampers on systems having return fans.
Classes II and III are appropriate for zone dampers where more
leakage is acceptable. Classes III and IV are applicable to dampers
that always modulate, such as in stairwell pressurization systems.

FIRE DAMPERS

Fire dampers are used in HVAC systems to prevent superheated
air, gases, or flames from crossing a fire barrier through an air
duct. Fire dampers are usually not used in modulating airflow
control applications and are designed for extreme operating
environments. Fire dampers are rated in hours of exposure in a
specified test environment. Construction and performance of fire
dampers (Fig. 11 and 12) is governed by UL Standard 555.
Fig. 11. Wall/Partition Fire Damper.
Fig. 12. Ceiling Fire Dampers.
ENGINEERING MANUAL OF AUTOMATIC CONTROL
450
M10413
M10416

Advertisement

Table of Contents
loading

Table of Contents