Control Applications; Ddc Control Of High Performance Substation - Honeywell AUTOMATIC CONTROL SI Edition Engineering Manual

For commercial buildings
Table of Contents

Advertisement

The primary side includes shut off valves, differential
pressure, and flow control equipment provide safety functions
and a required differential pressure or flow. Heat metering is
also included. The water flow here is divided into two parts.
The HEX transfers the heat from the primary system to the
DHW loop. A valve placed in series with the HEX controls the
flow. The other part of the primary flow enters the secondary
PRIMARY SUPPLY
PRIMARY RETURN

CONTROL APPLICATIONS

DDC CONTROL OF HIGH PERFORMANCE SUBSTATION

Reference
LIC 56
Water level supervision & control
LIC 63
Water level supervision & control
PDIC 14
Primary differential pressure
PDIC 45
Secondary differential pressure
PI 13
PSF pressure
PI 16
PRF pressure (internal)
PI 46
SRF pressure
PI 110
PRF pressure (outdoor)
PIC 57
SSF pressure
PLC
S9000 Supervisory Control
PSA+ 52
Safety pressure limit (refill pipe)
PSA+ 58
Safety pressure limit (SSF)
PZA+ 24
Safety pressure limit (high)
PZA+ 34
Safety pressure limit (high)
PZA+ 43
Safety pressure limit (SSF high)
PZA-27
Safety pressure limit (low)
PZA-37
Safety pressure limit (low)
PZA–42
Safety pressure limit (SSF total low)
QIR 53
Metering refill quantity
QIR 62
Cold water metering
QIR 111
Heat metering
TI 01
Outdoor air temperature
TI 12
PSF temperature
TI 15
PRF temperature (total flow)
TI 21
PRF temperature (HEX 1)
ENGINEERING MANUAL OF AUTOMATIC CONTROL
CHILLER, BOILER, AND DISTRIBUTION SYSTEM CONTROL APPLICATIONS
PRESSURE
CONTROL
P=CONSTANT
HEAT
EXCHANGER
(DHW)
Fig. 135. Hybrid Heat Transfer Substation.
Table 10. Description of Figure 136 Reference Points.
Description
circuit and transfers the heat to the consumer directly. The
supply flow temperature is controlled by one three-way valve,
two two-way valves, or one jet pump making an additional
circulation pump redundant.
In cases without a jet pump, circulation pumps provide the
needed differential pressure.
Reference
TI 31
PRF temperature (HEX 12)
TI 47
SRF temperature
TIC 28
SSF temperature (HEX 1)
TIC 38
SSF temperature (HEX 12)
TIC 44
SSF temperature
TSA+ 22
High temperature limit Primary Return Flow
Heat exchanger 1 (PRF HEX 1)
TSA+ 32
High temperature limit (PRF HEX 12)
TSA+ 25
High temperature limit (SSF HEX 1)
TSA+ 35
High temperature limit (SSF HEX 12)
TZA+ 26
Safety temperature limit (SSF HEX 1, locked)
TZA+36
High temperature limit (SSF HEX 12, locked)
TZA+ 41
Safety temperature limit (SSF total, high)
Y 11
Actuator valve Primary Supply Flow (PSF)
Y 17, Y 18
Actuator control valve (PDPC)
Y 19
Safety close off valve
Y 23
Actuator control valve
Y 29
Damper (secondary flow, HEX 1)
Y 33
Actuator control valve
Y 39
Damper (secondary flow, HEX 12)
Y 48, Y 49
Secondary flow circulating pumps
Y 51
Actuator valve (water refill from PRF)
Y 54
Vent valve
Y 55
Compressor
Y 61
Actuator valve (cold water refill)
Y 64
Feed water pump
387
DHW SUPPLY
DHW RECIRCULATED/
COLD WATER
HEATING SUPPLY
HEATING RETURN
M11433
Description