Honeywell AUTOMATIC CONTROL SI Edition Engineering Manual page 259

For commercial buildings
Table of Contents

Advertisement

15,16
Hot water valve modulates to maintain SA
temperature setpoint.
17
Free cooling demand varies SA temperature
setpoint.
18
Chilled water cooling demand varies SA
temperature setpoint.
19
Chilled water valve modulates to maintain SA
temperature cooling setpoint.
20
MA temperature sensor for operator
information.
21
OA temperature sensor for operator
information.
22
Control program coordinates space and supply
cooling, heating, and ventilation control, and
fan interlock.
FEATURES
1. Use of space control resetting SA temperature control adds
stability. The MA sensor is required to prevent freeze-up if
the free cooling setpoint is lowered in freezing weather.
2. SA temperature is maintained only as high or low as
required to meet space requirements.
3. Free cooling cycle selection determined by the
economizer control program to minimize load on
mechanical cooling system.
4. Optimum comfort temperature provided during free
cooling cycle with energy conserving deadbands for
heating and cooling.
CONDITIONS FOR SUCCESSFUL OPERATION
1. Sensor locations must be selected to measure
representative air conditions.
2. SA temperature control loops should provide PI control
to assure stability with minimum offset.
NOTE: In cold climates this unit would most often have the
heating coil ahead of the cooling coil and the low
temperature switch after the heating coil. Control
would not change. In the configuration shown, it
would be possible to add a dehumidification cycle
with reheat (software) at a later time.
SPECIFICATIONS
See FAN SYSTEM START-STOP CONTROL.
Anytime the supply fan runs, control system shall be enabled,
and mixing dampers shall position to minimum ventilation
position during scheduled occupancy periods.
Anytime the economizer decision program determines that
OA is suitable to assist in cooling, the temperature controls
shall be enabled to override the dampers minimum ventilation
position for free cooling as required.
ENGINEERING MANUAL OF AUTOMATIC CONTROL
AIR HANDLING SYSTEM CONTROL APPLICATIONS
The space temperature shall have a free cooling PI loop setpoint
selected to provide optimum occupant comfort temperature. The
space temperature shall have a chilled water cooling PI loop
setpoint adjustable to no lower than 0.8 kelvins (minimum) above
the free cooling setpoint. The space temperature shall have a
heating PI loop setpoint adjustable to no higher than 0.8 kelvins
(minimum) below the free cooling setpoint.
As the space heating load varies from 100 to 0%, an SA
heating PI control loop setpoint shall vary from 41 C to 13 C.
The hot water valve shall modulate to maintain the heating SA
temperature setpoint, except that anytime the space temperature
is greater than one degree above the free cooling space
temperature setpoint, the hot water valve control PI setpoint
shall be 11 C.
As the space free cooling load varies from 0 to 100%, an SA
free cooling PI control loop setpoint shall vary from 24 C to
14 C. The mixing dampers shall modulate to maintain the free
cooling SA temperature setpoint.
As the space chilled water cooling load varies from 0 to 100%,
an SA chilled water cooling PI control loop setpoint shall vary
from 24 C to 13 C. The chilled water valve shall modulate to
maintain this cooling SA temperature setpoint.
PSYCHROMETRIC ASPECTS
In the following chart it is assumed that:
1. OA condition is 18 C and 53% RH.
2. System is in the economizer mode.
COOLING COIL
DISCHARGE 15 C
2
1
COIL
100% OA
COOLING
18 C DB, 53% RH
LOAD
The following results are obtained:
Item
No.
Explanation
1
100% economizer air is entering the cooling
coil.
2
The chilled water coil cools the entering air
to its 15 C setpoint (removing little moisture
because the water flow is low and the OA
moisture content is not high).
3
Space temperature is 24.5 C and 38% RH.
249
SPACE
3
24.5 C DB, 38% RH
M15177

Advertisement

Table of Contents
loading

Table of Contents