Circuits
LED Indicators
•
Fire Alarm Zone 1 - red LED
•
Fire Alarm Zone 2 - red LED
•
Fire Alarm Zone 3 - red LED (Flex 404 only)
•
Fire Alarm Zone 4 - red LED (Flex 404 only)
•
Supervisory Zone 1 - yellow LED
•
Supervisory Zone 2 - yellow LED
•
Supervisory Zone 3 - yellow LED (Flex 404 only)
•
Supervisory Zone 4 - yellow LED (Flex 404 only)
•
Trouble Zone 1 - yellow LED
•
Trouble Zone 2 - yellow LED
•
Trouble Zone 3 - yellow LED (Flex 404 only)
•
Trouble Zone 4 - yellow LED (Flex 404 only)
•
Maintenance Zone 1 - yellow LED
•
Maintenance Zone 2 - yellow LED
•
Maintenance Zone 3 - yellow LED (Flex 404 only)
•
Maintenance Zone 4 - yellow LED (Flex 404 only)
•
AC Power - green LED
•
NAC Disable - yellow LED
•
Zone Disable - yellow LED
•
NAC Fault - yellow LED
•
System Trouble - yellow LED
•
Power Trouble - yellow LED
•
Walktest - yellow LED
•
Alarm Silence - yellow LED
•
Earth Fault - yellow LED (on main circuit board) lights if zero impedance between FACP and
ground exists
•
Battery Fault - yellow LED (on main circuit board)
•
Charger Fault - yellow LED (on main circuit board)
Local Piezo Sounder
A piezo sounder provides separate and distinct sounds for alarm, trouble, maintenance and
supervisory conditions as follows:
•
Alarm - on steady
•
Trouble - pulse 1 second on and 1 second off
•
Maintenance - pulse ½ second on and ½ second off
•
Supervisory - pulse ½ second on and ½ second off
1.4 Circuits
Input Circuits
Two input IDCs (Initiating Device Circuits) on the Flex 402 and four IDCs on the Flex 404 provide
Style B (Class B) configurations. All IDCs accept i
smoke detectors, four-wire smoke detectors and normally-open contact devices.
Output Circuits
•
24 VDC resettable special application power output - 500 mA
•
24 VDC nonresettable special application power output (Flex 404 only) - 500 mA
Flex 402 & Flex 404 Instruction Manual — P/N 52194:D4 3/27/2015
detectors as well as conventional two-wire
3
Product Description
13