Diagnosing The Ied Status Via The Lhmi Hint Menu - Hitachi Relion SAM600 Commissioning Manual

Switchgear control unit
Table of Contents

Advertisement

Section 11
Troubleshooting
Module that should be changed.
Sequence of faults, if more than one unit is faulty.
Exact time when the fault occurred.
11.2.3

Diagnosing the IED status via the LHMI hint menu

In order to help the user, there is an LHMI page labeled 'Hints'. This page is located under Main
menu/Diagnostics/IED status/Hints. For each activated hint there is a headline. From the headline
view, an explanation page can be entered, giving the user more information and hints about the
particular topic.
The supported list of hints are as follows:
Table 14:
Headline
Check if the following parameters are set correctly on
PMUREPORT:1 ReportRate or SvcClass or RptTimetag
or parameter PRIMVAL:1.FrequencySel is not set as
50Hz / 60Hz.
GOOSE is configured on a disabled port
OEM not running the application image
Merging unit has no access point
Mismatching data batch size to DistRep
LDCM missing connections
LDCM system frequency
Table continues on next page
62
The Hint menu is currently only available in English. All the entries are in English,
regardless of which language is selected.
Hint menu
© 2017 - 2023 Hitachi Energy. All rights reserved
Explanation
At least one of the access points configured for GOOSE is
disabled. The port can be disabled either through
changing the access point operation to off or by
unchecking the GOOSE protocol from the access point in
the Ethernet configuration in PCM600 or LHMI.
Enable GOOSE on access points:
<Access Points>, can be any of these: AP_FRONT,
AP_1, AP_2, AP_3, AP_4, AP_5, AP_6,AP_7, AP_8
OEM in pos <slot number> is running the factory image
instead of the application image. The factory image is
older than the required FW version and does not contain
the latest updates and fixes.
Reboot the IED. If the problem persists, update the OEM
firmware or replace the board.
Merging unit has no access point.
Check AP configuration.
Check cycle time for SMAI and 3PHSUM blocks
connected to Disturbance Report blocks. SMAI and
3PHSUM blocks shall have the same cycle time.
LDCM transmitter is missing connections. Check the
LDCMTRN block.
System frequency is different in local and remote end of
LDCM link.
Check the parameter FrequencySel at both ends.
Switchgear control unit SAM600-IO
1MRK511447-UEN Rev. E
GUID-7E8503E9-441B-487A-9CD7-B43463D1CAE5 v6
Commissioning manual