Using Lhmi Service Kit-Connected Pc - Hitachi Relion SAM600 Commissioning Manual

Switchgear control unit
Table of Contents

Advertisement

1MRK511447-UEN Rev. E
Using the LHMI service kit, the present information from the self-supervision function can be viewed.
Indications of failure or warnings for each hardware module are provided, as well as information
about the external time synchronization and the internal clock. All according to table 11. Loss of time
synchronization can be considered as a warning only. The IED has full functionality without time
synchronization.
11.2.2

Using LHMI service kit-connected PC

Using a LHMI service kit, extensive information about an internal fault can be retrieved from the list of
internal events available in the SMS part:
TRM-STAT TermStatus - Internal Events
The list of internal events provides valuable information, which can be used during commissioning
and fault tracing.
The internal events are time tagged with a resolution of 1ms and stored in a list. The list can store up
to 40 events. The list is based on the FIFO principle, when it is full, the oldest event is overwritten.
The list cannot be cleared and its content cannot be erased.
The internal events in this list not only refer to faults in the IED, but also to other activities, such as
change of settings, clearing of disturbance reports, and loss of external time synchronization.
The information can only be retrieved from the Parameter Setting software package. The PC can be
connected either to the port at the front or at the rear of the IED.
These events are logged as internal events.
Table 12:
Event message:
INT--FAIL
INT--FAIL
INT--WARNING
INT--WARNING
IOn--Error
IOn--Error
ADMn-Error
ADMn-Error
MIM1-Error
MIM1-Error
INT--RTC
INT--RTC
INT--TSYNC
INT--TSYNC
INT--SETCHGD
DRPC-CLEARED
The events in the internal event list are time tagged with a resolution of 1ms.
This means that, when using the PC for fault tracing, it provides information on the:
Switchgear control unit SAM600-IO
Commissioning manual
Events available for the internal event list in the IED
Description
Off
Internal fail status
Off
Internal warning status
Off
In/Out module No. n status
Off
Analog/Digital module No. n
status
Off
mA-input module status
Off
Real Time Clock (RTC) status
Off
External time synchronization
status
Any settings in IED changed
All disturbances in Disturbance
report cleared
© 2017 - 2023 Hitachi Energy. All rights reserved
Generating signal:
INT--FAIL (reset event)
INT--FAIL (set event)
lNT--WARNING (reset event)
lNT--WARNING (set event)
IOn--Error (reset event)
IOn--Error (set event)
ADMn-Error (reset event)
ADMn-Error (set event)
MIM1-Error (reset event)
MIM1-Error (set event)
INT--RTC (reset event)
INT--RTC (set event)
INT--TSYNC (reset event)
INT--TSYNC (set event)
Section 11
Troubleshooting