Dehumidification Configuration

Name
Cfg_DehumEnable
Cfg_Dehum_SpaceRHHighLimit
Cfg_Dehum_OverCool_Offset
Cfg_Dehum_StageReHeatOpEn
Cfg_DehumAuxHeatForReheat

Fan configuration

Name
Cfg_FanType
Cfg_FanRunOffDelayCool
Cfg_FanRunOnDelayHeat
Cfg_FanRunOffDelayHeat
Dehumidification Configuration
Table 16 Dehumidification configuration
BACnet
BACnet
Object
Object
Type
Instance
Binary
2040
Value
Analog
48
Value
Analog
2022
Value
Binary
133
Value
Binary
2041
Value
Table 17 Fan configuration
BACnet
BACnet
Object
Object
Type
Instance
Multistate
12
Value
Analog
39
Value
Analog
40
Value
Analog
2017
Value
Default
Range
Value
0
Off=0,
On=1
65%RH
30 to 100%RH
-2 °F
-5 to -1 °F
0
Disable=0,
Enable=1
0
Disable=0,
Enable=1
Default
Range
Value
1
enum{SingleSpeed=1,
TwoSpeed=2,
ThreeSpeed=3,
VariableSpeed=4}
0
0 to 180 seconds
seconds
30
0 to 30 seconds
seconds
120
0 to 180 seconds
seconds
Description
Enable/disable
dehumidification
Space relative humidity
(RH) high limit setpoint.
Dehumidification over
cool offset
Staged reheat operation
enable
Aux heat reheat enable
Description
Fan can be
configured as
single speed,
two speed or
as a variable
speed fan.
Fan run on
time after all
cooling
terminal turns
off.
Fan run on
delay time
after heating
terminal turns
on.
Fan run on
time after all
heating
terminal turns
off