Terminal Input; Terminal Output And Network Output - Honeywell TC300 Integration Manual

Bacnet integration guide
Hide thumbs Also See for TC300:
Table of Contents

Advertisement

Terminal input

Name
phy_ChangeOverSwitch
phy_DatSensor
phy_DrainpanSensor
phy_OccupancySensor
phy_ProofOfAirFlowSensor
phy_PipeSensor
phy_SpaceTempSensor

Terminal output and network output

Name
no_SixWay_Valve_Cooling
no_SixWay_Valve_Heating
no_Modulating_Cool
no_Modulating_Heat
no_VariableFan
no_Auxiliary_Heat
no_ChangeOverValve
no_Cooling_Valve(On/Off)
no_Heating_Valve(On/Off)
32
Table 5 Terminal input
BACnet
BACnet
Object
Object
Type
Instance
Binary Input
1
Analog
1
Input
Binary Input
2
Binary Input
3
Binary Input
4
Analog
2
Input
Analog
3
Input
Table 6 Terminal output and network output
BACnet
BACnet
Object
Object
Type
Instance
Analog
2001
Output
Analog
2002
Output
Analog
2003
Output
Analog
2004
Output
Analog
2005
Output
Binary
2001
Output
Binary
2002
Output
Binary
2004
Output
Binary
2005
Output
Default
Range
Value
0
Close=0,
Open=1
-40 to 200 °F
0
Off=0,
On=1
0
Standby=0
Unoccupied=1
0
Off=0
On=1
-40 to 260 °F
-40 to 150 °F
Range
0 to 100%
Six-way valve cooling control output
0 to 100%
Six-way valve Heating control output
0 to 100%
Modulating cool control output
0 to 100%
Modulating heat control output
0 to 100%
Variable Fan control output
Off=0,On=1
Auxiliary heat control output
Off=0,On=1
Changeover valve control output
Off=0,On=1
Cooling on/off valve output status
Off=0,On=1
Heating on/off valve output status
Description
Changeover switch
status
Discharge air sensor
output value
Drain pan sensor status
Occupancy sensor status
Proof of air flow sensor
status
Pipe sensor output value
Space temperature
sensor output value
Description