Gas pressure sensors DGS
TECHNICAL INFORMATION
• Digital connection facilities for smart gas sections
• Pressure gauge and pressure transmitter in a single device
• Minimum installation effort
• Predictive maintenance
• Analyses for trends/system optimization
• Local and remote monitoring (Thermal IQ™)
• Suitable for hydrogen
EN
Edition 09.23
03251656

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell krom schroder DG Smart

  • Page 1 Gas pressure sensors DGS TECHNICAL INFORMATION • Digital connection facilities for smart gas sections • Pressure gauge and pressure transmitter in a single device • Minimum installation effort • Predictive maintenance • Analyses for trends/system optimization • Local and remote monitoring (Thermal IQ™) •...
  • Page 2: Table Of Contents

    Contents Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 6.3 Non-safety parameters .
  • Page 3 9 Output signal coding . . . . . . . . . . . . . . . . . . . . . . . . .24 10 Project planning information .
  • Page 4: Application

    1 Application 1 Application The pressure sensor DG smart is a relative and differential pressure sensor which monitors the MIN/MAX and/or differ- ential pressure for gas, air, flue gas or other non-aggressive gases. DG smart meets the current requirements of DIN EN 1854:2022 (Class A and C) and international stand- ards which require the safety function of MAX/MIN monitor- ing and shut-down.
  • Page 5: Application Examples

    2 Application examples 2 Application examples 2 .2 Low and high gas pressure protection at the gas inlet section 2 . 1 Air line with MIN, MAX pressure monitoring PZL/ PZL/ VSBV If the pressure is either too high or too low (PZL/PZH), the gas pressure sensor prevents the system starting or trig- gers a safety shut-down.
  • Page 6: Certification

    3 Certification 3 Certification 3 . 1 Certificate download Certificates – see www.docuthek.com 3 .2 Declaration of conformity We, the manufacturer, hereby declare that the productDG smart complies with the requirements of the listed Direc- tives and Standards. Directives: • 2014/30/EU – EMC •...
  • Page 7: Function

    4 Function 4 Function 4 .3 Differential pressure sensor Differential pressure measurement is used, for example, to 4 . 1 Transmitter-, MIN-/MAX function safeguard an air flow rate or to monitor filters and fans. The sensor records the difference between ports P1 and The pressure is detected by a sensor, processed and com- municated via an analog value on the display and made available for signal processing to the higher-level control...
  • Page 8: Part Designations

    4 Function 4 .4 Part designations 4 .5 Electrical connection 4 .5 . 1 Voltage supply and 4–20 mA signal Connect the 24 V DC voltage supply using the M12 con- nector (plug/plug, 4-pin, A-coded). 1 Upper housing section Function 2 Lower housing section 3 Display 4–20 mA 4 Status display...
  • Page 9: Leds (Colour/Flash Code)

    4 Function 4 .6 LEDs (colour/flash code) Colour Meaning Mode Description The pressure is greater than the Two changing colour LEDs show the status of the MAX/MIN setting values for the “MIN function or a message. Green Permanent alarm”, “MIN warning” and “MIN »...
  • Page 10: Selection

    5 Selection 5 Selection 5 . 1 . 1 Connections 1 or 2 for positive pressure Rp ¼ ( ¼" NPT) 5 . 1 Selection table 3 Breather orifice Description Code DGS Condition Gas pressure sensor • Relative pressure (positive pressure) Relative pressure sensor measuring range (positive pressure) Connect Seal...
  • Page 11: Parameter

    6 Parameter 6 Parameter 6 . 1 General The “Parameters” menu option is divided into “Safety pa- rameters” (password-protected) and “Non-safety parame- ters”. The value ranges of the parameters can be edited on the DG smart or using the integral web server. 6 .2 Safety parameters All safety parameters are password-protected.
  • Page 12: Sensor Function

    6 Parameter 6 .2 . 1 Sensor function 6 .2 .5 MIN reset Sensor function Value range Description Parameter settings: Automatic Reset logic for the MIN function is set to automatic. Transmitter 3. Event ... Reset logic for the MIN function is set to manual. (On- Confirm Cancel Manual...
  • Page 13: Non-Safety Parameters

    6 Parameter 6 .3 Non-safety parameters Name Translation Value range Factory default settings MAX warning MAX warning Setting 0 mbar MAX alarm MAX alarm Setting 0 mbar MIN warning MIN warning Setting 0 mbar MIN alarm MIN alarm Setting 0 mbar IP address* Communication Kommunikation Subnet* Gateway* 192.168.0.200...
  • Page 14: Settings

    6 Parameter 6 .4 Settings Settings Display Passwort Display Name Translation Value range Factory default settings Measuring unit Measuring unit mbar, kPa, PSI, inch WC mbar Decimal separator Decimal separator Point “.” or comma “,” Point “.” Brightness Brightness Setting: Display brightness 100% Temperature unit Temperature unit...
  • Page 15: Password

    6 Parameter 6 .4 .6 Password A four-digit numerical password enables the user to restrict access to the unit. Password-protected parameters can only be edited on the DG smart or using the web server if the user is logged in. 6 .5 Statistics Name Translation Value range...
  • Page 16: Device Statistics

    6 Parameter 6 .5 .2 Device statistics 6 .5 .5 Clear customer statistics Device statistics are provided for diagnostic purposes and The customer statistics can be reset by the user (login re- cannot be reset by the customer. They cover the entire ser- quired).
  • Page 17: Information

    6 Parameter 6 .6 Information Name Translation Value range Device name Gerätname The device name, network configuration and firmware are Network Network displayed in plain text. Firmware Firmware 6 .6 . 1 Device name 6 .6 .3 Network The device name is displayed. The current network configuration is displayed.
  • Page 18: Web Server

    7 Web server 7 Web server The web server can be accessed using the preset IP ad- dress 192.168.0.200 (subnet mask 255.255.255.0). The IP address of the computer must be in the same network as the DGS for the parameterization process. The IP address can be changed using the “Communication”...
  • Page 19 7 Web server Device and customer statistics The event history and customer statistics can be reset if the user is logged in. Service Process data are displayed in the “Service” section. A firm- ware upgrade can be performed if the user is logged in. DG smart ·...
  • Page 20: Modbus Tcp

    8 Modbus TCP 8 Modbus TCP 8 . 1 . 1 Process data The Modbus protocol is a communications protocol based Register Description Value range/Unit Relative pressure at P1 mbar (signed) on a Client/Server architecture. Once the TCP/IP connec- Relative pressure at P2 mbar (signed) tion between client (PLC) and server (DG smart) has been...
  • Page 21: Event History

    8 Modbus TCP 8 . 1 .2 Event history 8 . 1 .3 Device statistics Register 57348 Counters and extreme values Value range/ Number of registers: 80 (8 registers per event) Register Description Unit The event history saves the last 10 events in the structure 3456 Power On counter Low word...
  • Page 22: Customer Statistics

    8 Modbus TCP 8 . 1 .4 Customer statistics Fault counter Register Description Counters and extreme values 3510 Too many remote resets Too many remote resets Value range/ Register Description 3552 Permant remote reset Permanent remote reset Unit Error supply voltage too low/too 3756 Power On counter Low word...
  • Page 23: Safety Parameters

    8 Modbus TCP 8 . 1 .6 Safety parameters 8 . 1 .8 Hardware parameters Register 57386 Register 57389 Number of registers: 9 Number of registers: 1 Offset Register Description Value range/Unit Offset Register Description Value range 0 = Transmitter 0 = ePSD Cat A, 100 mbar 1 = MIN 1 = ePSD Cat A, 350 mbar...
  • Page 24: Output Signal Coding

    9 Output signal coding 9 Output signal coding The 4–20 mA output supplies the current pressure in the form of an analog value. The pressure measuring range is scaled to 4–20 mA. The Recommendation NAMUR NE43 (standardization of the signal level for the failure information of digital transmit- ters with an analog output signal) is used as a reference for standardized error information (in addition to the measuring information).
  • Page 25: Project Planning Information

    10 Project planning information 10 Project planning information 10 .2 MIN and MAX switching point range The MIN/MAX switching value must be within the specified 10 . 1 Installation MAX/MIN switching point range. See Technical data, meas- uring range, page 29 (12.4 Measuring range). Long-term use in the upper ambient temperature range ac- The switching point is set in the safety parameters, see celerates the ageing of the elastomer materials and reduces...
  • Page 26: Accessories

    11 Accessories 11 Accessories 11 . 1 Test key PIA Tube set with 2 m PVC tube, 2 duct connection flanges with screws, R 1/4 and R 1/8 connecting nipples. Order No.: 74912952. To test the min. pressure switch, the DG smart can be 11 .3 Fastening set with screws, U-shape vented in its switched state using the PIA test key (contains bracket...
  • Page 27: Connecting Set For Dgs And Dg

    11 Accessories 11 .4 Connecting set for DGS and DG A DGS used as a relative pressure sensor (positive pres- sure) can be connected to a pressure switch (DG..U, DG..B, DG..H, DG..N) with a mechanical switching function. Order No.: 74912250 DG smart ·...
  • Page 28: Technical Data

    12 Technical data 12 Technical data The gas must be clean and dry in all temperature conditions and must not contain condensate. Max. inlet pressure p = withstand pressure, 12 . 1 Ambient conditions max. measuring range and max. deviations, see page 29 (12.4 Icing, condensation and dew in and on the unit are not per- Measuring range).
  • Page 29: Measuring Range

    12 Technical data Functional earth: ground terminal for connecting fine-strand 12 .4 . 1 Overall accuracy to EN 1854:2022 cables up to 4 mm The overall accuracy E of a specific inlet pressure is calcu- lated on the basis of various factors. Internal fuse: replaceable fuse (slow-acting, 200 mA).
  • Page 30: Dimensions

    12 Technical data 12 .6 Dimensions DGS..R: Rp ¼ (DGS..N: ¼" NPT) 4 x ø 3,6 44 (1.7") (4 x ø 0.14") 84 (3.3") DG smart · Edition 09.23 · EN...
  • Page 31: Converting Units

    13 Converting units 13 Converting units See www.adlatus.org DG smart · Edition 09.23 · EN...
  • Page 32: Maintenance Cycles

    14 Maintenance cycles 14 Maintenance cycles In order to ensure smooth operation, check the tightness and function of the pressure sensor every year. » After carrying out the maintenance work, check for tight- ness. A zero point adjustment must be carried out at operating temperature after the maintenance work has been complet- ed to ensure the best possible accuracy.
  • Page 33: Cyber And It Security

    15 Cyber and IT security 15 Cyber and IT security 15 .2 Securing the network The digitalization of production provides plenty of versatility A securely planned, designed and operated network ar- for collecting and using data. A secure network configura- chitecture ensures that network access delivers adequate tion must be established to provide protection from cyber security.
  • Page 34: Communications Protocols

    15 Cyber and IT security 15 .4 Recommendations and time-tested The correct configuration depends on the manufacturer’s requirements for the individual system components. methods Higher-level PLC/control centre The following instructions are designed to ensure that the • Configure the operating system and the relevant software unit is installed safely and operated in a safe communica- in accordance with the recommendations of the manu- tion environment.
  • Page 35: Reporting Vulnerabilities

    Honeywell reviews all vulnerability reports relating to Honeywell products and services. For further information, see www.honeywell.com/prod- uct-security. Report a vulnerability for a Honeywell product in the Report A Vulnerability Issue section. DG smart · Edition 09.23 · EN...
  • Page 36: Open Source Software Licences

    16 Open source software licences 16 Open source software licences Freely available software was used to create the DG smart. For the terms and conditions of the open source software licences, see www.docuthek.com, OSS Licenses. DG smart · Edition 09.23 · EN...
  • Page 37: Glossary

    17 Glossary 17 Glossary 17 . 1 Regulating and control functions Class A (ePSD Cat A): regulating and control functions which are not designed for the safety of the application to be dependent on them. Class C (ePSD Cat C): regulating and control functions which are designed to prevent specific hazards, such as explosions, or whose failure may directly result in a hazard in the unit.
  • Page 38: For More Information

    For more information The Honeywell Thermal Solutions family of products includes Honeywell Combustion Safety, Eclipse, Exothermics, Hauck, Kromschröder and Maxon. To learn more about our products, visit ThermalSolutions.honey- well.com or contact your Honeywell Sales Engineer. Elster GmbH © 2023 Elster GmbH...