Honeywell Ex-Or MR1500P Installation And Commissioning Instructions

Honeywell Ex-Or MR1500P Installation And Commissioning Instructions

Mid range lightspot

Advertisement

MR1500P / MR1500PF
Mid Range LightSpot
MR1500P
MR1500PF
Installation and Commissioning
Instructions
Note: QuickSet Pro required for commissioning

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell Ex-Or MR1500P

  • Page 1 MR1500P / MR1500PF Mid Range LightSpot MR1500P MR1500PF Installation and Commissioning Instructions Note: QuickSet Pro required for commissioning...
  • Page 2 Mid Range LightSpot (Switching) Fixing Only suitably qualified personnel should install this equipment. 1. The Mid Range LightSpot is an extremely sensitive movement detector; it is essential therefore that it be installed on a rigid surface that will not itself be subject to any movement or vibration. 2.
  • Page 3 Electrical Connections Mid Range LightSpot should be connected in accordance with the diagram below. Mid Range LightSpot is designed to control a switched load of up to 10 Amps. When switching via the relay output, multiple MR1500Ps' relay outputs may be connected in parallel provided the controlled load does not exceed 10 Amps.
  • Page 4 Commissioning The units are supplied with the factory default settings shown below which render commissioning unnecessary in many applications. To make use of the programmable settings, an infrared commissioning tool is required (QuickSet Pro). A ten-second time delay is selectable to aid commissioning. Sensitivity to Movement While the factory settings will be correct for many applications, the sensitivity can be adjusted if required.
  • Page 5 Photocell Control i) Switching Photocell (PHOTOCELL: ACTIVE or PASSIVE) Both ACTIVE or PASSIVE modes hold off the controlled lighting on entry when natural light is sufficient, i.e. SET-POINT LOW is exceeded, but only ACTIVE mode will extinguish the lighting if natural light increases sufficiently during occupancy, i.e.
  • Page 7 Important Additional Notes All terminals on this product are provided for final connections. It is not intended that the product be used as a junction box for looping cables. Take care when choosing a location for this equipment since this type of device is capable of detecting large moving metal objects well beyond the normal range at which it is sensitive to human targets.
  • Page 8 IP RATING: 4X OPERATING TEMPERATURE: 0 C to 40 C Contact Ex-Or Technical Helpline on 01942 719229 for guidance on installation and commissioning. Honeywell Ex-Or St. Marks Court, North Street, At the end of their useful life Horsham, West Sussex, RH12 1BW, UK.

This manual is also suitable for:

Ex-or mr1500pf

Table of Contents