Event History; Device Statistics - Honeywell krom schroder DG Smart Technical Information

Gas pressure sensors
Table of Contents

Advertisement

8 Modbus TCP

8 . 1 .2 Event history

Register 57348
Number of registers: 80 (8 registers per event)
The event history saves the last 10 events in the structure
described below.
Offset Description
0
Event time
1
Event time
2
Error code
3
Supply voltage
4
Temperature
5
High byte event
5
Low byte short error code
6
Pressure
7
Operating status
DG smart · Edition 09.23 · EN
Value range/Unit
Low word of the time
High word of the time
V * 10
K * 10
Event IDs:
1 = Device error
2 = Fault lock-out
3 = Safety shut-down
4 = Warning
8 = Error
9 = Parameter changed
10 = Statistics deleted
11 = Power On
12 = System error
13 = Login failed
mbar * 10
0 = Initialization
1 = Normal operation
4 = Underpressure warning
5 = Underpressure error
6 = Overpressure error
7 = Temperature drift error
8 = Sensor drift error
9 = Defective sensor

8 . 1 .3 Device statistics

Counters and extreme values
Register Description
3456
Power On counter
3457
Power On counter
4378
Reset counter
4379
Reset counter
3458
Total duty cycle
3459
Total duty cycle
4650
Max. duty cycle duration
4651
Max. duty cycle duration
4654
Max. overtemperature duration
4655
Max. overtemperature duration
4390
Extreme value: Maximum temperature
4391
Extreme value: Minimum temperature
5139
Extreme value: Maximum pressure
5140
Extreme value: Minimum pressure
Fault counter
Register
3210
Too many remote resets
3252
Permant remote reset
3232
Error under-/overvoltage
Warning/Error undertempera-
3413
ture
3416
Warning/Error overtemperature
3275
MIN pressure
3276
MAX pressure
3277
Error underpressure
3278
Error overpressure
3273
4–20 mA interrupted
3274
4–20 mA impedance error
3299
Internal error
Value range/
Unit
Low word
High word
Low word
High word
Low word
High word
Low word
High word
Low word
High word
Low word, K * 10
High word, K * 10
Low word, mbar * 10
High word, mbar * 10
Description
Too many remote resets
Permanent remote reset
Error supply voltage too low/too
high
Warning/error ambient tempera-
ture low
Warning/error ambient tempera-
ture high
MIN switching pressure
MAX switching pressure
Underpressure error
Overpressure error
4–20 mA signal missing/inter-
rupted.
4–20 mA signal impedance er-
ror
Internal device error