9 Output signal coding

9 Output signal coding
The 4–20 mA output supplies the current pressure in the
form of an analog value. The pressure measuring range is
scaled to 4–20 mA.
The Recommendation NAMUR NE43 (standardization of
the signal level for the failure information of digital transmit-
ters with an analog output signal) is used as a reference for
standardized error information (in addition to the measuring
information).
Current
range [mA]
22.0
21.0
MAX switching pressure detected
21.0
20.5
20.0
4.0
3.8
3.6
3.0
MIN switching pressure detected
2.0
Over-/undervoltage or over-/undertemperature detected
1.0
0
Output off (internal or device error)
DG smart · Edition 09.23 · EN
Description
Overpressure detected
Upper error range
Upper tech range
Upper nominal range
Lower nominal range
Lower tech range
Lower error range
Underpressure detected