EBL512 G3 V. 3.0.X - FIRE ALARM SOLUTIONS OPERATING INSTRUCTIONS

31.4. DISPLAY CURRENT CONSUMPTION IN UNIT (H5/A4)

POWER SUPPLY (CONTROL UNIT)
Voltage: The 24V measured by the CPU on the main board. Corresponds to the output voltage at the power supply outputs on
connector J3.
Earth voltage: Measured from 0V (connector J4:2) to earth.
Current from power supply: The total current consumption (including the charging current at 24V) for the selected control unit
(c.i.e.) when it is connected to the mains (230 V AC), i.e. this function is not working by battery backup.
BATTERY
Voltage: The battery voltage at connector J4:4-5.
Charging current: The battery charging current for the selected control unit (c.i.e.).
Temperature: The temperature detected by the battery temperature sensor.
Resistance in battery circuit: During the battery capacity check the resistance in the battery circuit is measured. A resistance >
500 mΩ will result in a "Low battery capacity" fault. Checked every 15 minutes.
a) Log on to the c.i.e.
b) Navigate to menu A4.
c) Write control unit number and press
d) Please wait.
Power supply (control unit xx)
Voltage: xx.xx V
Earth voltage: xx.xx V
Current from power supply: xxx mA
Battery
Voltage: xx.xx V
Charging current: x mA
Temperature xx°C
Resistance in battery circuit: xxxxx mΩ
e) To exit the menu press
The information is automatically updated every 5th second.
If you get "No reply from control unit....." the control unit don't exist or don't answer.
.
or ESC.
107