1MRK506375-UEN Rev. N
ArgLd: To set the load angle determining the load impedance area of the load discrimination
characteristic. Set the parameter to the maximum possible load angle at maximum possible load.
The default value is set at 30 deg.
OpModeI0: To select the operation On or Off of the end zone timer logic using residual overcurrent
start to provide a remote backup.
OpModetEnd1: To select operation On or Off of the end timer 1.
OpDirEnd1: To select the direction mode of end timer 1. It can be set to Non-directional, Forward and
Reverse. It is recommended to set as Forward.
tEnd1: To set time delay for the first stage remote backup (end timer 1). The setting should allow the
farthest zone to operate. The default setting is 2.5 s.
OpModetEnd2: To select the operation On or Off of the end timer 2.
OpDirEnd2: To select the direction mode of the end timer 2. It can be set to Non-directional, Forward
and Reverse. It is recommended to set this as Non-directional.
tEnd2: To set the time delay for the second stage backup (end timer 2). It should be set in
coordination with the tEnd1 timer. The default setting is 3.0s.
OpModeGenSt: To select On or Off of zone timers start by general start signal. The default value is
Off.
ZoneCharSym: To select measuring zone Symmetry/Nonsymmetry around R – X plane and it is set
by default to Symmetry. With this default value, it is not possible to set resistive and reactance
reaches in reverse direction. However, if it is needed to specify the reverse reaches depending on
the application, it is recommended to set this parameter to Nonsymmetry.
Start
CharStartZ<: To select the underimpedance start characteristic (i.e. Circular and Quadrilateral).
Z1CircleStart: To set a positive sequence impedance reach in Ohm of the starting element circular
characteristic. It will be set to operate for all faults within the protected area. Therefore, it should be
set beyond the reach of the farthest zone.
X1Start: To set positive sequence reactance reach in Ohm of starting element quadrilateral
characteristic. It will be set to operate for all faults within the protected area. Therefore, it should be
set beyond the reach of the farthest zone.
RFPEStart: To set the forward and reverse resistive reach in Ohm for PE starting element when the
quadrilateral characteristic is selected. It will be set to a value greater than the resistive reach of the
farthest zone.
RFPPStart: To set the forward and reverse resistive reach in Ohm for PP starting element when the
quadrilateral characteristic is selected. It will be set to a value greater than the resistive reach of the
farthest zone. It is not applicable for compensated and high impedance earthed systems.
I0MinOp: The minimum operating current of residual overcurrent start as % of IBase. It should be set
to detect all earth faults, but above any continuous residual current under normal operating
conditions. The default value is 10% IB.
KI0Stab: The stabilizing factor to prevent operation of the residual overcurrent start caused by an
unbalance or dissimilar CT behaviour in the event of high short circuit currents. The default setting is
0.8.
Direction
ArgNegRes: The angle for blinder in the second quadrant. The default setting is 120 deg and it
should not be changed unless system studies show the necessity.
Railway application RER670
Application manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 7
Impedance protection
GUID-D2A63BD2-34EA-407C-B43F-165DCB576C4E v4
GUID-02B0EB72-B881-4FFC-A488-AC5014820F7C v3
93